59
“b” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units

B012 Level of electronic thermal U A

B212 Level of electronic thermal,
2nd motor
Set a level between 20% and 100%
for the rated inverter current.
U
Rated
current for
each
inverter
model *1
A
B013 Electronic thermal
characteristic
U 01
B213 Electronic thermal
characteristic, 2nd motor
Select from three curves, option
codes:
00Reduced torque
01Constant torque
02Free setting
U 01
b015 Free setting electronic thermal
~freq.1
Range is 0 to 400Hz U 0.0 Hz
b016 Free setting electronic thermal
~current1
Range is 0 to inverter rated current
Amps U 0.00
Amps
b017 Free setting electronic thermal
~freq.2
Range is 0 to 400Hz U 0.0 Hz
b018 Free setting electronic thermal
~current2
Range is 0 to inverter rated current
Amps
U 0.00
Amps
b019 Free setting electronic thermal
~freq.3
Range is 0 to 400Hz U 0.0 Hz
b020 Free setting electronic thermal
~current3
Range is 0 to inverter rated current
Amps
U 0.00
Amps
B021 Overload restriction operation
mode
U 01
B221 Overload restriction operation
mode, 2nd motor
Select the operation mode during
overload conditions, four options,
option codes:
00Disabled
01Enabled for acceleration and
constant speed
02Enabled for constant speed
only
03Enabled for acceleration and
constant speed, increase speed
at regen.
U 01

B022 Overload restriction level U Rated

current
x 1.5
Amps
B222 Overload restriction level,
2nd motor
Sets the level of overload restriction,
between 20% and 200% of the rated
current of the inverter, setting
resolution is 1% of rated current U Rated
current
x 1.5
Amps
B023 Deceleration rate at overload
restriction U 1.0 sec.
B223 Deceleration rate at overload
restriction, 2nd motor
Sets the deceleration rate when
inverter detects overload, range is
0.1 to 3000.0, resolution 0.1 U 1.0 sec.
b024 Overload restriction operation
mode 2
Select the operation mode during
overload conditions, four options,
option codes:
00Disabled
01Enabled for acceleration and
constant speed
02Enabled for constant speed
only
03Enabled for acceleration and
constant speed, increase speed
at regen.
U 01