Run

 

 

 

 

 

 

 

 

Func.

 

Name

 

 

 

Description

 

 

Mode

 

 

Initialdata

 

 

 

Units

 

Code

 

 

 

 

 

 

 

 

Edit

 

 

 

 

 

 

 

 

B012

 

Level of electronic thermal

 

 

 

Set a level between 20% and 100%

 

 

 

 

 

Rated

 

 

 

A

 

B212

 

Level of electronic thermal,

 

 

 

for the rated inverter current.

 

 

 

 

 

current for

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

each

 

 

 

 

 

 

2nd motor

 

 

 

 

 

 

 

 

 

inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

model *1

 

 

 

 

 

B013

 

Electronic thermal

 

 

 

Select from three curves, option

 

 

 

 

 

01

 

 

 

 

 

 

characteristic

 

 

 

codes:

 

 

 

 

 

 

 

 

 

 

 

B213

 

Electronic thermal

 

 

 

00Reduced torque

 

 

 

 

 

01

 

 

 

 

 

 

characteristic, 2nd motor

 

 

 

01Constant torque

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02Free setting

 

 

 

 

 

 

 

 

 

 

 

b015

 

Free setting electronic thermal

 

 

 

Range is 0 to 400Hz

 

 

 

 

 

0.0

 

 

 

Hz

 

 

 

~freq.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b016

 

Free setting electronic thermal

 

 

 

Range is 0 to inverter rated current

 

 

 

 

 

0.00

 

 

 

Amps

 

 

 

~current1

 

 

 

Amps

 

 

 

 

 

 

 

 

 

 

 

b017

 

Free setting electronic thermal

 

 

 

Range is 0 to 400Hz

 

 

 

 

 

0.0

 

 

 

Hz

 

 

 

~freq.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b018

 

Free setting electronic thermal

 

 

 

Range is 0 to inverter rated current

 

 

 

 

 

0.00

 

 

 

Amps

 

 

 

~current2

 

 

 

Amps

 

 

 

 

 

 

 

 

 

 

 

b019

 

Free setting electronic thermal

 

 

 

Range is 0 to 400Hz

 

 

 

 

 

0.0

 

 

 

Hz

 

 

 

~freq.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b020

 

Free setting electronic thermal

 

 

 

Range is 0 to inverter rated current

 

 

 

 

 

0.00

 

 

 

Amps

 

 

 

~current3

 

 

 

Amps

 

 

 

 

 

 

 

 

 

 

 

B021

 

Overload restriction operation

 

 

 

Select the operation mode during

 

 

 

 

 

01

 

 

 

 

 

 

mode

 

 

 

overload conditions, four options,

 

 

 

 

 

 

 

 

 

 

 

B221

 

Overload restriction operation

 

 

 

option codes:

 

 

 

 

 

01

 

 

 

 

 

 

mode, 2nd motor

 

 

 

00Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Enabled for acceleration and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

constant speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02Enabled for constant speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03Enabled for acceleration and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

constant speed, increase speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at regen.

 

 

 

 

 

 

 

 

 

 

 

B022

 

Overload restriction level

 

 

 

Sets the level of overload restriction,

 

 

 

 

 

Rated

 

 

 

Amps

 

 

 

 

 

 

 

between 20% and 200% of the rated

 

 

 

 

 

current

 

 

 

 

 

 

 

 

 

 

 

current of the inverter, setting

 

 

 

 

 

x 1.5

 

 

 

 

 

 

 

Overload restriction level,

 

 

 

resolution is 1% of rated current

 

 

 

 

 

 

 

 

 

 

B222

 

 

 

 

 

 

 

 

 

Rated

 

 

 

Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2nd motor

 

 

 

 

 

 

 

 

 

current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x 1.5

 

 

 

 

 

B023

 

Deceleration rate at overload

 

 

 

Sets the deceleration rate when

 

 

 

 

 

1.0

 

 

 

sec.

 

 

 

restriction

 

 

 

inverter detects overload, range is

 

 

 

 

 

 

 

 

 

 

 

B223

 

Deceleration rate at overload

 

 

 

0.1 to 3000.0, resolution 0.1

 

 

 

 

 

1.0

 

 

 

sec.

 

 

 

restriction, 2nd motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b024

 

Overload restriction operation

 

 

 

Select the operation mode during

 

 

 

 

 

01

 

 

 

 

 

 

mode 2

 

 

 

overload conditions, four options,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Enabled for acceleration and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

constant speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02Enabled for constant speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03Enabled for acceleration and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

constant speed, increase speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at regen.

 

 

 

 

 

 

 

 

 

 

 