Option

 

 

Terminal

 

 

Function Name

 

 

 

Description

 

 

 

Code

 

 

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29

 

 

UDC

 

Remote Control Data

 

ON

Clears the UP/DWN frequency memory by forcing it to

 

 

 

 

 

 

 

 

 

Clearing

 

 

equal the set frequency parameter F001. Setting C101

 

 

 

 

 

 

 

 

 

 

 

 

 

must be set=00 to enable this function to work

 

 

 

 

 

 

 

 

 

 

 

 

OFF

UP/DWN frequency memory is not changed

 

 

 

31

 

 

OPE

Operator Control

 

ON

Forces the source of the output frequency setting A001

 

 

 

 

 

 

 

 

 

 

 

 

 

and the source of the Run command A002 to be from

 

 

 

 

 

 

 

 

 

 

 

 

OFF

the digital operator

 

 

 

 

 

 

 

 

 

 

 

 

 

Source of output frequency set by A001 and source of

 

 

 

 

 

 

 

 

 

 

 

 

 

Run command set by A002 is used

 

 

 

32

 

 

SF1

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 1, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 1

 

OFF

Bit encoded speed select, Bit 1, logical 0

 

 

 

33

 

 

SF2

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 2, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 2

 

OFF

Bit encoded speed select, Bit 2, logical 0

 

 

 

34

 

 

SF3

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 3, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 3

 

OFF

Bit encoded speed select, Bit 3, logical 0

 

 

 

35

 

 

SF4

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 4, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 4

 

OFF

Bit encoded speed select, Bit 4, logical 0

 

 

 

36

 

 

SF5

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 5, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 5

 

OFF

Bit encoded speed select, Bit 5, logical 0

 

 

 

37

 

 

SF6

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 6, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 6

 

OFF

Bit encoded speed select, Bit 6, logical 0

 

 

 

38

 

 

SF7

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 7, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 7

 

OFF

Bit encoded speed select, Bit 7, logical 0

 

 

 

39

 

 

OLR

 

Overload Restriction

 

ON

Perform overload restriction

 

 

 

 

 

 

 

 

 

Source Changeover

 

OFF

Normal operation

 

 

 

 

40

 

 

TL

 

Torque Limit Selection

 

ON

Setting of b040 is enabled

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Max. torque is limited with 200%

 

 

 

41

 

 

TRQ1

Torque limit switch 1

 

ON

Torque limit related parameters of Powering/regen, and

 

 

 

 

 

 

 

 

 

 

 

 

OFF

FW/RV modes are selected by the combinations of

 

 

 

42

 

 

TRQ2

Torque limit switch 2

 

ON

these inputs.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

44

 

 

BOK

Brake confirmation

 

ON

b124

) is valid

 

 

 

 

 

 

 

 

 

 

 

OFF

Brake wait time (

 

 

 

 

 

 

 

 

 

 

 

 

b124

) is not valid

 

 

 

 

 

 

 

 

 

 

 

 

 

Brake wait time (

 

 

 

46

 

 

LAC

 

LAD cancellation

 

ON

Set ramp times are ignored. Inverter output

 

 

 

 

 

 

 

 

 

 

 

 

 

immediately follows the freq. command.

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Accel. and/or decel. is according to the

 

 

 

 

 

 

 

 

 

 

 

 

 

set ramp time

 

 

 

 

47

 

 

PCLR

 

Pulse counter clear

 

ON

Clear the position deviation data

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Maintain the position deviation data

 

 

 

50

 

 

ADD

ADD frequency enable

 

ON

Adds the A145 (add frequency) value

 

 

 

 

 

 

 

 

 

 

 

 

OFF

to the output frequency

 

 

 

 

 

 

 

 

 

 

 

 

Does not add the A145 value to the

 

 

 

 

 

 

 

 

 

 

 

 

 

output frequency

 

 

 

 

51

 

 

F-TM

 

Force Terminal Mode

 

ON

Force inverter to use input terminals

 

 

 

 

 

 

 

 

 

 

 

 

OFF

for output frequency and Run command sources

 

 

 

 

 

 

 

 

 

 

 

 

Source of output frequency set by A001 and source of

 

 

 

 

 

 

 

 

 

 

 

 

 

Run command set by A002 is used

 

 

 

52

 

 

ATR

 

Enable torque

 

ON

Torque control command input is enabled

 

 

 

 

 

 

 

 

 

command input

 

OFF

Torque control command input is disabled

 

 

 

53

 

 

KHC

 

Clear watt-hour data

 

ON

Clear watt-hour data

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No action

 

 

 

 

56

 

 

MI1

General purpose input

 

ON

General purpose input (1) is made ON under EzSQ

 

 

 

 

 

 

 

 

(1)

 

 

OFF

General purpose input (1) is made OFF under EzSQ

 

 

 

57

 

 

MI2

General purpose input

 

ON

General purpose input (2) is made ON under EzSQ

 

 

 

 

 

 

 

 

(2)

 

 

OFF

General purpose input (2) is made OFF under EzSQ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

73

Page 75
Image 75
Hitachi hitachi series inverter user manual SF1, SF2, SF3, SF4, SF5, SF6, SF7, Olr, Off Bok, MI1, MI2