Func.

 

Name

 

Description

 

 

Code

 

 

 

 

 

 

 

 

 

Run

Mode

Edit

Initialdata Units

 

a131

Acceleration curve constant

Range is 01 to 10.

 

02

 

 

 

 

 

 

 

 

 

 

a132

Deceleration curve constant

Range is 01 to 10.

 

02

 

 

 

 

 

 

 

 

 

A141

A input select for calculate

Seven options:

 

02

 

 

function

00

 

 

 

 

 

 

 

Operator

 

 

 

 

 

 

 

01VR

 

 

 

 

 

 

 

02Terminal [O] input

 

 

 

 

 

 

 

03Terminal [OI] input

 

 

 

 

 

 

 

04RS485

 

 

 

 

 

 

 

05Option

 

 

 

 

 

 

 

07Pulse train input

 

 

 

 

 

A142

B input select for calculate

Seven options:

 

03

 

 

function

00

 

 

 

 

 

 

 

Operator

 

 

 

 

 

 

 

01VR

 

 

 

 

 

 

 

02Terminal [O] input

 

 

 

 

 

 

 

03Terminal [OI] input

 

 

 

 

 

 

 

04RS485

 

 

 

 

 

 

 

05Option

 

 

 

 

 

 

 

07Pulse train input

 

 

 

 

 

A143

Calculation symbol

Calculates a value based on the

 

00

 

 

 

A input source (A141 selects) and

 

 

 

 

 

 

 

B input source (A142 selects).

 

 

 

 

 

 

 

Three options:

 

 

 

 

 

 

 

00ADD (A input + B input)

 

 

 

 

 

 

 

01SUB (A input - B input)

 

 

 

 

 

 

 

02MUL (A input * B input)

 

 

 

 

 

A145

ADD frequency

An offset value that is applied to

 

0.00

Hz

 

 

 

the output frequency when the

 

 

 

 

 

 

 

[ADD] terminal is ON.

 

 

 

 

 

 

 

Range is 0.0 to 400.0 Hz

 

 

 

 

 

A146

ADD direction select

Two options:

 

00

 

 

 

00Plus (adds A145 value to the

 

 

 

 

 

 

 

output frequency setting)

 

 

 

 

 

 

 

01Minus (subtracts A145 value

 

 

 

 

 

 

 

from the output frequency

 

 

 

 

 

 

 

setting)

 

 

 

 

 

a150

Curvature of EL-S-curve at the

Range is 0 to 50%

 

10.

%

 

 

 

start of acceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a151

Curvature of EL-S-curve at the

Range is 0 to 50%

 

10.

%

 

 

 

end of acceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a152

Curvature of EL-S-curve at the

Range is 0 to 50%

 

10.

%

 

 

 

start of deceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a153

Curvature of EL-S-curve at the

Range is 0 to 50%

 

10.

%

 

 

 

end of deceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a154

Deceleration hold frequency

Sets the frequency to hold

 

0.0

Hz

 

 

 

deceleration, range is 0.0 to

 

 

 

 

 

 

 

400.0Hz

 

 

 

 

 

a155

Deceleration hold time

Sets the duration of deceleration

 

0.0

sec.

 

 

 

hold, range is 0.0 to 60.0

 

 

 

 

 

 

 

seconds

 

 

 

 

56

Page 58
Image 58
Hitachi hitachi series inverter user manual A131, A132, A141, A142, A143, A145, A146, A150, A151, A152, A153, A154, A155