10
Determining Wire and Fuse Sizes The maximum motor currents in your application determines the recommended wore size.
The following table gives the wire size in AWG. The “Power Lines” column applies to the
inverter input power, output wires to the motor, the earth ground connection, and any other
components shown in the “Basic System Description” on page 9. The “Signal Lines”
column applies to any wire connecting to the two green connectors just inside the front
cover panel.
Motor Output Wiring Applicable
equipment
kW HP
VT CT VT CT
Inverter Model
Power Lines Signal Lines
Fuse (UL-rated,
class J, 600V ,
Maximum
allowable current)
0.2 0.1 ¼ 1/8 WJ200-001SF
0.4 0.2 ½ ¼ WJ200-002SF
0.55
0.4 ¾ ½ WJ200-004SF
AWG16 / 1.3mm2
(75°C only) 10A
1.1
0.75
1.5 1 WJ200-007SF AWG12 / 3.3mm2
(75°C only) 20A
2.2 1.5 3 2 WJ200-015SF
3.0 2.2 4 3 WJ200-022SF AWG10 / 5.3mm2 30A
0.2 0.1 ¼ 1/8 WJ200-001LF
0.4 0.2 ½ ¼ WJ200-002LF
0.75
0.4 1 ½ WJ200-004LF
10A
1.1
0.75
1.5 1 WJ200-007LF
AWG16 / 1.3mm2
2.2 1.5 3 2 WJ200-015LF AWG14 / 2.1mm2
(75°C only)
15A
3.0 2.2 4 3 WJ200-022LF AWG12 / 3.3mm2
(75°C only) 20A
5.5 3.7 7.5 5 WJ200-037LF AWG10 / 5.3mm2
(75°C only) 30A
7.5 5.5 10 7.5 WJ200-055LF
11 7.5 15 10 WJ200-075LF
AWG6 / 13mm2
(75°C only) 60A
15 11 20 15 WJ200-110LF AWG4 / 21mm2
(75°C only) 80A
18.5
15 25 20 WJ200-150LF AWG2 / 34mm2
(75°C only) 80A
0.75
0.4 1 ½ WJ200-004HF
1.5
0.75
2 1 WJ200-007HF
2.2 1.5 3 2 WJ200-015HF
AWG16 / 1.3mm2
3.0 2.2 4 3 WJ200-022HF
10A
4.0 3.0 5 4 WJ200-030HF AWG14 / 2.1mm2
5.5 4.0 7.5 5 WJ200-040HF AWG12 / 3.3mm2
(75°C only)
15A
7.5 5.5 10 7.5 WJ200-055HF
11 7.5 15 10 WJ200-075HF
AWG10/ 5.3mm2
(75°C only) 30A
15 11 20 15 WJ200-110HF AWG6 / 13mm2
(75°C only) 50A
18.5
15 25 20 WJ200-150HF AWG6 / 13mm2
(75°C only)
18 to 28
AWG / 0.14
to 0.75 mm2
shielded wire
(see Note 4)
50A