Analog Output Operation

In inverter applications it is useful to monitor the inverter operation from a remote location or from the front panel of an inverter enclosure. In some cases, this requires only a panel-mounted volt meter. In other cases, a controller such as a PLC may provide the inverter’s frequency command, and require inverter feedback data (such as output frequency or output current) to confirm actual operation. The analog output terminal [AM] serves these purposes.

 

AM

H

O

OI

L

Analog

+

 

 

 

 

-

Voltage

 

 

 

 

A GND

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10VDC full scale, 2mA max

See I/O specs on page 21,22

The inverter provides an analog voltage output on terminal [AM] with terminal [L] as analog GND reference. The [AM] can output inverter frequency or current output value. Note that the voltage range is 0 to +10V (positive-going only), regardless of forward or reverse motor rotation. Use C028 to configure terminal [AM] as indicated below.

 

 

 

 

00

Inverter output frequency

 

01

Inverter output current

 

02

Inverter output torque

 

03

Digital output freqnency

 

04

Inverter output goltage

 

05

Inverter input power

C028

06

Electronic Thermal Load

 

07

LAD frequency

 

08

Digital current monitor

 

10

Cooling fin temperature

 

12

General purpose

 

15

Pulse train

 

16

Option

44

Page 46
Image 46
Hitachi hitachi series inverter user manual Analog Output Operation, Gnd