Standard Functions

NOTE:. Mark “ ” in b031=10 shows the accessible parameters when b031 is set “10”, high level access.

 

 

 

 

 

 

 

 

Func.

 

Name

 

Description

 

 

Code

 

 

 

 

 

 

 

 

 

Run

Mode

Edit

Initialdata Units

A001

Frequency source

Eight options; select codes:

 

 

02

 

 

00

POT on ext. operator

 

 

 

 

 

 

01

Control terminal

 

 

 

 

A201

Frequency source,

02

Function F001 setting

 

 

02

2nd motor

03

Modbus network input

 

 

 

 

 

 

04

Option

 

 

 

 

 

 

06

Pulse train input

 

 

 

 

 

 

07

via EzSQ

 

 

 

 

 

 

10

Calculate function output

 

 

 

 

A002

Run command source

Four options; select codes:

 

 

02

 

 

01

Control terminal

 

 

 

 

 

Run command source,

02

Run key on keypad, or

 

 

 

 

A202

 

digital operator

 

 

02

2nd motor

03

Modbus network input

 

 

 

 

 

 

04

Option

 

 

 

 

A003

Base frequency

Settable from 30 Hz to the

 

 

60.0

Hz

 

 

maximum frequency(A004)

 

 

 

 

A203

Base frequency,

Settable from 30 Hz to the 2nd

 

 

 

Hz

 

 

60.0

2nd motor

maximum frequency(A204)

 

 

 

 

 

 

 

 

 

A004

Maximum frequency

Settable from the base

 

60.0

Hz

 

 

frequency to 400 Hz

 

 

 

A204

Maximum frequency,

Settable from the 2nd base

 

 

Hz

60.0

2nd motor

frequency to 400 Hz

 

 

 

 

 

 

 

 

 

A005

[AT] selection

Three options; select codes:

 

00

 

 

00...Select between [O] and [OI]

 

 

 

 

 

 

at [AT] (ON=OI, OFF=O)

 

 

 

 

 

02...Select between [O] and

 

 

 

 

 

 

external POT at [AT]

 

 

 

 

 

 

(ON=POT, OFF=O)

 

 

 

 

 

03...Select between [OI] and

 

 

 

 

 

 

external POT at [AT]

 

 

 

 

 

 

(ON=POT, OFF=OI)

 

 

 

A011

[O] input active range start

The output frequency

 

0.00

Hz

frequency

corresponding to the analog

 

 

 

 

 

input range starting point,

 

 

 

 

 

range is 0.00 to 400.0

 

 

 

A012

[O] input active range end

The output frequency

 

0.00

Hz

frequency

corresponding to the analog

 

 

 

 

 

input range ending point,

 

 

 

 

 

range is 0.0 to 400.0

 

 

 

A013

[O] input active range start

The starting point (offset) for the

 

0.

%

voltage

active analog input range,

 

 

 

 

 

range is 0. to 100.

 

 

 

A014

[O] input active range end

The ending point (offset) for the

 

100.

%

voltage

active analog input range,

 

 

 

 

 

range is 0. to 100.

 

 

 

50

Page 52
Image 52
Hitachi hitachi series inverter user manual Standard Functions