79
“H” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units
H231 Motor constant R2,
2
nd
motor
(Auto tuned data)
U ohm
H032 Motor constant L
(Auto tuned data) U mH
H232 Motor constant L,
2
nd
motor
(Auto tuned data)
0.01~655.35mH
U mH
H033 Motor constant I0
(Auto tuned data) U A
H233 Motor constant I0,
2
nd
motor
(Auto tuned data)
0.01~655.35A
U A
H034 Motor constant J
(Auto tuned data) U kgm2
H234 Motor constant J,
2
nd
motor
(Auto tuned data)
0.001~9999 kgm2
U
kgm2
H050 Slip compensation P gain
for V/f control with FB
0.00-10.00 U 0.2 Times
H051 Slip compensation I gain
for V/f control with FB
0.-1000. U 2. (s)
PM Motor Constants Functions
“H” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units

H102 PM motor code setting

00Hitachi standard
(Use H106-H110 at motor
constants)
01Auto-Tuning
(Use H109-H110, H111-H113
at motor constants)
U
00
-
H103 PM motor capacity 0.1/0.2/0.4/0.55/0.75/1.1/1.5/2.2/
3.0/3.7/4.0/5.5/7.5/11.0/15.0/18.5
U kW
dependent kW
H104 PM motor pole setting 2/4/6/8/10/12/14/16/18/20/22/24/26/
28/30/32/34/36/38/40/42/44/46/48 U kW
dependent Poles
H105 PM Rated Current (0.00-1.00)×Rated current of the
inverter [A]
U kW
dependent A

H106 PM const R(Resistance) 0.001-65.535 [] U kW

dependent Ohm
H107 PM const Ld
(d-axis inductance)
0.01-655.35 [mH] U kW
dependent mH
H108 PM const Lq
(q-axis inductance)
0.01-655.35 [mH] U kW
dependent mH
H109 PM const Ke
(Induction voltage constant)
0.0001-6.5535 [V/(rad/s)] U kW
dependent V/(rad/
s)
H110 PM const J
(Moment of inertia)
0.001-9999.000 [kgm2] U kW
dependent kgm^2
H111 PM const R
(Resistance, Auto)
0.001-65.535 [] U kW
dependent Ohm