Monitoring functions

NOTE:. Mark “ ” in b031=10 shows the accessible parameters when b031 is set “10”, high

level access.

* Please change from"04 (Basic display)" to "00 (Full display)" in parameter

B037 (Function code display restriction), in case some parameters cannot be displayed.

IMPORTANT

Please be sure to set the motor nameplate data into the appropriate parameters to ensure proper operation and protection of the motor:

b012 is the motor overload protection value

A082 is the motor voltage selection

H003 is the motor kW capacity

H004 is the number of motor poles

Please refer to the appropriate pages in this guide and the Instruction Manual for further details.

 

 

 

 

 

 

 

 

 

Run

Units

Func.

Name

Description

 

Mode

Code

 

Edit

 

Output frequency monitor

Real time display of output frequency

Hz

D001

 

 

to motor from

 

 

 

 

 

 

 

 

 

 

0.0 to 400.0Hz

 

 

 

 

 

 

 

 

 

If b163 is set high, output frequency

 

 

 

 

(F001) can be changed by up/down

 

 

 

 

key with d001 monitoring.

 

 

 

D002

Output current monitor

Filtered display of output current to

A

 

 

motor, range is

 

 

 

 

 

 

 

 

 

0 to 655.3 ampere (~99.9 ampere for

 

 

 

 

1.5kW and less)

 

 

 

 

 

 

D003

Rotation direction monitor

Three different indications:

 

 

 

FForward

 

 

 

 

 

 

 

 

 

oStop

 

 

 

 

 

 

 

 

 

 

rReverse

 

 

 

 

 

 

 

D004

Process variable (PV),

Displays the scaled PID process

% times

 

PID feedback monitor

variable (feedback) value (A075 is

 

constant

 

 

scale factor),

 

 

 

 

 

 

 

 

 

 

0.00 to 10000

 

 

 

 

 

 

 

D005

Intelligent input

Displays the state of the intelligent

 

terminal status

input terminals:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

7

6

5

4

3

2

1

 

 

 

 

Terminal numbers

 

 

 

 

46

Page 48
Image 48
Hitachi hitachi series inverter user manual Monitoring functions