Error

 

 

Name

 

 

Cause(s)

 

 

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E81

 

 

Excessive speed

 

 

If the motor speed rises to "maximum frequency

 

 

 

 

 

 

 

 

(A004) x over-speed error detection level (P026)" or more,

 

 

 

 

 

 

 

 

the inverter will shut off its output and display the error

 

 

 

 

 

 

 

 

code shown on the right.

 

 

E83

 

 

Positioning range error

 

If current position exceeds the position range

 

 

 

 

 

 

 

 

(P072-P073), the inverter will shut off its output and

 

 

 

 

 

 

 

 

display the error code.

 

Other indication

 

Error

 

 

Name

 

 

Descriptions

 

 

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rotating

 

 

Reset

 

 

RS input is ON or STOP/RESET key is pressed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Undervoltage

 

 

If input voltage is under the allowed level, inverter shuts

 

 

 

 

 

 

 

off output and wait with this indication.

 

 

 

 

 

 

 

 

 

 

 

 

 

Waiting to restart

 

 

This indication is displayed after tripping before

 

 

 

 

 

 

 

restarting.

 

 

 

 

 

 

 

 

 

 

 

 

 

Restricted operation

 

 

Commanded RUN direction is restricted in b035.

 

 

 

 

 

command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Trip history initializing

 

 

Trip history is being initialized.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No data

 

 

No trip/waning data exists.

 

 

 

 

 

(Trip monitor)

 

 

 

 

 

 

 

 

 

 

 

 

Blinking

 

 

Communication error

 

 

Communication between inverter and digital operator

 

 

 

 

 

 

 

fails.

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto-tuning

 

 

Auto-tuning is completed properly.

 

 

 

 

 

completed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto-tuning error

 

Auto-tuning fails.

 

 

 

 

 

 

 

 

 

 

NOTE: Reset is not allowed in 10 second after trip.

NOTE: When error E08, E14 and E30 occur, reset operation by RS terminal or STOP/RESET key is not accepted. In this case, reset by cycling power. If still same error occurs, perform initialization.

Restoring Factory Default Settings

You can restore all inverter parameters to the original factory (default) settings according to area of use. After initializing the inverter, use the powerup test in Chapter 2 to get the motor running again. If operation mode (std. or high frequency) mode is changed, inverter must be initialized to activate new mode. To initialize the inverter, follow the steps below.

(1)Select initialization mode in b084.

(2)If b084=02, 03 or 04, select initialization target data in b094.

(3)If b084=02, 03 or 04, select country code in b085.

(4)Set 01 in b180.

(5)The following display appears for a few seconds, and initialization is completed with

d001 displayed.

* Please change from"0 4 (Basic display)" to "0 0 (Full display)" in parameter

B 0 3 7 (Function code display restriction), in case some parameters cannot be displayed.

87

Page 89
Image 89
Hitachi hitachi series inverter Restoring Factory Default Settings, Other indication, Error Name Descriptions Code