70
“C” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units
C102 Reset selection Determines response to Reset
input [RS].
Four option codes:
00Cancel trip state at input signal
ON transition, stops inverter if
in Run Mode
01Cancel trip state at signal OFF
transition, stops inverter if in
Run Mode
02Cancel trip state at input ON
transition, no effect if in Run
Mode
03Clear the memories only
related to trip status
U 00
C103 Restart mode after reset Determines the restart mode after
reset is given, three option codes:
00Start with 0 Hz
01Start with freq. matching
02Start with active freq. matching
U 00 -
C104 UP/DWN clear mode Freq. set value when UDC signal is
given to the input terminal, two
option codes:
000 Hz
01Original setting (in the
EEPROM memory at power
on)
U 00 -
C105 EO gain adjustment Set range is 50 to 200% 100. % C106 AM gain adjustment Set range is 50 to 200% 100. % C109 AM bias adjustment Set range is 0 to 100% 0. %
C111 Overload warning level 2 Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Rated current
x 1.15
A
C130 Output [11] on delay U 0.0 Sec.
C131 Output [11] off delay
Set range is 0.0 to 100.0 sec.
U 0.0 Sec.
C132 Output [12] on delay U 0.0 Sec.
C133 Output [12] off delay
Set range is 0.0 to 100.0 sec.
U 0.0 Sec.
C140 Relay output on delay U 0.0 Sec.
C141 Relay output off delay
Set range is 0.0 to 100.0 sec.
U 0.0 Sec.
C142 Logic output 1 operand A U 00
C143 Logic output 1 operand B
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no U 00
C144 Logic output 1 operator Applies a logic function to calculate
[LOG] output state,
Three options:
00[LOG] = A AND B
01[LOG] = A OR B
02[LOG] = A XOR B
U 00
C145 Logic output 2 operand A U 00
C146 Logic output 2 operand B
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no U 00