Fuse Sizes

Distribution fuse size marking is included in the manual to indicate that the unit shall be connected with a Listed Cartridge Nonrenewable fuse, rated 600 Vac with the current ratings as shown in the table below or Type E Combination Motor Controller marking is included in the manual to indicate that the unit shall be connected with,LS Industrial System Co.,Ltd,Type E Combination Motor Controller MMS Series with the ratings as shown in the table below:

Inverter Model

Type

Fuse Rating

Type E CMC

WJ200-001S WJ200-002S WJ200-004S

WJ200-007S

WJ200-015S WJ200-022S

WJ200-001L WJ200-002L WJ200-004L

WJ200-007L WJ200-015L

WJ200-022L

WJ200-037L

WJ200-055L WJ200-075L

WJ200-110L WJ200-150L

WJ200-004H WJ200-007H WJ200-015H WJ200-022H

WJ200-030H WJ200-040H

WJ200-055H WJ200-075H

WJ200-110H WJ200-150H

Class J

10A, AIC 200kA

 

 

MMS-32H,240V,40A

20A, AIC 200kA

 

30A, AIC 200kA

 

 

 

10A, AIC 200kA

 

 

MMS-32H,240V,40A

15A, AIC 200kA

 

 

 

20A, AIC 200kA

 

30A, AIC 200kA

 

60A, AIC 200kA

 

 

MMS-100H,240V,80A

80A, AIC 200kA

 

 

 

10A, AIC 200kA

 

 

MMS-32H,480V,40A

15A, AIC 200kA

or

 

MMS-63H,480V,52A

30A, AIC 200kA

 

 

 

50A, AIC 200kA

 

 

 

3

Page 5
Image 5
Hitachi hitachi series inverter user manual Fuse Sizes