“b” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units
b037 Function code display
restriction
Six option codes:
00…Full display
01…Function-specific display
02…User setting (and b037)
03…Data comparison display
04…Basic display
05…Monitor display only
U 04 −
b038 Initial display selection 000…Func. code that SET key
pressed last displayed.(*)
001~030…d001~d030 displayed
201…F001 displayed
202…B display of LCD operator
U 001 − B039 Automatic user parameter
registration
Two option codes:
00…Disable
01…Enable
U 00 B040 Torque limit selection Three option codes:
00…Quadrant-specific setting mode
01…Terminal-switching mode
02…Analog voltage input mode(O)
U 00 B041 Torque limit 1 (fwd/power) Torque limit level in forward
powering quadrant, range is 0 to
200%/no(disabled)
U 200 % b042
B043 Torque limit 3 (rev/power) Torque limit level in reverse
powering quadrant, range is 0 to
200%/no(disabled)
U 200 % B044 Torque limit 4 (fwd/regen.) Torque limit level in forward regen.
quadrant, range is 0 to
200%/no(disabled)
U 200 % b045 Torque LAD STOP selection Two option codes:
00…Disable
01…Enable
U 00 b046 Reverse run protection Two option codes:
00…No protection
01…Reverse rotation is protected
U 01 −
b049 Dual Rating Selection 00… (CT mode) / 01… (VT mode) U 00
B050 Controlled deceleration on
power loss
Four option codes:
00…Trips
01…Decelerates to a stop
02…Decelerates to a stop with DC
bus voltage controlled
03…Decelerates to a stop with DC
bus voltage controlled, then
restart
U 00 − B051 DC bus voltage trigger level of
ctrl. decel.
Setting of DC bus voltage to start
controlled decel. operation. Range is
0.0 to 1000.0
U 220.0/ 440.0
V
B052 Over-voltage threshold of ctrl.
decel.
Setting the OV-LAD stop level of
controlled decel. operation. Range is
0.0 to 1000.0
U 360.0/ 720.0
V
B053 Deceleration time of ctrl. decel. Range is 0.01 to 3600.0 U 1.0 sec
B054 Initial freq. drop of ctrl. decel. Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
U 0.0 Hz