61
“b” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units
b037 Function code display
restriction
Six option codes:
00Full display
01Function-specific display
02User setting (and b037)
03Data comparison display
04Basic display
05Monitor display only
U 04
b038 Initial display selection 000Func. code that SET key
pressed last displayed.(*)
001~030d001~d030 displayed
201F001 displayed
202B display of LCD operator
U 001
B039 Automatic user parameter
registration
Two option codes:
00Disable
01Enable
U 00
B040 Torque limit selection Three option codes:
00Quadrant-specific setting mode
01Terminal-switching mode
02Analog voltage input mode(O)
U 00
B041 Torque limit 1 (fwd/power) Torque limit level in forward
powering quadrant, range is 0 to
200%/no(disabled)
U 200 %
b042
B043 Torque limit 3 (rev/power) Torque limit level in reverse
powering quadrant, range is 0 to
200%/no(disabled)
U 200 %
B044 Torque limit 4 (fwd/regen.) Torque limit level in forward regen.
quadrant, range is 0 to
200%/no(disabled)
U 200 %
b045 Torque LAD STOP selection Two option codes:
00Disable
01Enable
U 00
b046 Reverse run protection Two option codes:
00No protection
01Reverse rotation is protected
U 01
b049 Dual Rating Selection 00 (CT mode) / 01 (VT mode) U 00
B050 Controlled deceleration on
power loss
Four option codes:
00Trips
01Decelerates to a stop
02Decelerates to a stop with DC
bus voltage controlled
03Decelerates to a stop with DC
bus voltage controlled, then
restart
U 00
B051 DC bus voltage trigger level of
ctrl. decel.
Setting of DC bus voltage to start
controlled decel. operation. Range is
0.0 to 1000.0
U 220.0/
440.0
V
B052 Over-voltage threshold of ctrl.
decel.
Setting the OV-LAD stop level of
controlled decel. operation. Range is
0.0 to 1000.0
U 360.0/
720.0
V

B053 Deceleration time of ctrl. decel. Range is 0.01 to 3600.0 U 1.0 sec

B054 Initial freq. drop of ctrl. decel. Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
U 0.0 Hz