Hitachi hitachi series inverter user manual Run Signal When the inverter is in Run Mode

Models: hitachi series inverter

1 99
Download 99 pages 42.08 Kb
Page 77
Image 77

Output Function Summary Table – This table shows all functions for the logical outputs (terminals [11], [12] and [AL]) at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Output Terminals” on page 36.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

 

 

Terminal

 

 

Function Name

 

 

 

Description

 

 

 

 

 

Code

 

 

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

 

 

RUN

 

Run Signal

 

ON

When the inverter is in Run Mode

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When the inverter is in Stop Mode

 

 

 

 

01

 

 

FA1

 

Frequency Arrival Type

 

ON

When output to motor is at the set frequency

 

 

 

 

 

 

 

 

1–Constant Speed

 

OFF

When output to motor is OFF, or in any

 

 

 

 

 

 

 

 

 

 

 

acceleration or deceleration ramp

 

 

 

 

02

 

 

FA2

 

Frequency Arrival Type

 

ON

When output to motor is at or above the set freq,

 

 

 

 

 

 

 

 

2–Over frequency

 

 

 

C042

 

C043

) ramps

 

 

 

 

 

 

 

 

 

 

 

even if in accel (

 

) or decel (

 

 

 

 

 

 

 

 

 

 

 

OFF

When output to motor is OFF,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or at a level below the set frequency

 

 

 

03

 

 

OL

Overload Advance

 

ON

When output current is more than the set

 

 

 

 

 

 

 

 

Notice Signal 1

 

 

threshold (C041) for the overload signal

 

 

 

 

 

 

 

 

 

 

OFF

When output current is less than the set threshold

 

 

 

 

 

 

 

 

 

 

 

for the deviation signal

 

 

 

 

 

04

 

 

OD

Output Deviation

 

ON

When PID error is more than the set threshold for

 

 

 

 

 

 

 

 

for PID Control

 

 

the deviation signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When PID error is less than the set threshold for

 

 

 

 

 

 

 

 

 

 

 

the deviation signal

 

 

 

 

 

 

05

 

 

AL

 

Alarm Signal

 

ON

When an alarm signal has occurred and has not

 

 

 

 

 

 

 

 

 

 

 

been cleared

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When no alarm has occurred since the last

 

 

 

 

 

 

 

 

 

 

 

cleaning of alarm(s)

 

 

 

 

 

 

06

 

 

FA3

 

Frequency Arrival Type

 

ON

When output to motor is at the set frequency,

 

 

 

 

 

 

 

 

3–Set frequency

 

 

during accel (

C042

) and decel (

C043

).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

When output to motor is OFF,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or is not at a level of the set frequency

 

 

07

 

 

OTQ

 

Over/under Torque

 

ON

Estimated motor torque exceeds

 

 

 

 

 

 

 

 

 

 

Signal

 

 

the specified level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Estimated motor torque is lower than

 

 

 

 

 

 

 

 

 

 

 

the specified level

 

 

 

 

 

 

 

09

 

 

UV

Undervoltage

 

ON

Inverter is in Undervoltage

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Inverter is not in Undervoltage

 

 

 

 

 

10

 

 

TRQ

Torque Limited Signal

 

ON

Torque limit function is executing

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Torque limit function is not executing

 

 

 

11

 

 

RNT

 

Run Time Expired

 

ON

Total running time of the inverter exceeds

 

 

 

 

 

 

 

 

 

 

 

the specified value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Total running time of the inverter does not exceed

 

 

 

 

 

 

 

 

 

 

 

the specified value

 

 

 

 

 

 

12

 

 

ONT

 

Power ON time Expired

 

ON

Total power ON time of the inverter exceeds

 

 

 

 

 

 

 

 

 

 

 

the specified value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Total power ON time of the inverter does not

 

 

 

 

 

 

 

 

 

 

 

exceed the specified value

 

 

 

 

 

13

 

 

THM

Thermal Warning

 

ON

Accumulated thermal count exceeds

 

 

 

 

 

 

 

 

 

 

 

 

the C061 set value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Accumulated thermal count does not exceed the

 

 

 

 

 

 

 

 

 

 

 

C061 set value

 

 

 

 

 

 

 

19

 

 

BRK

Brake Release Signal

 

ON

Output for brake release

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No action for brake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

BER

Brake Error Signal

 

ON

Brake error has occurred

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Brake performance is normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

Page 77
Image 77
Hitachi hitachi series inverter user manual Run Signal When the inverter is in Run Mode