55
“A” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units
A092 Acceleration time (2) 10.00 sec
A292 Acceleration time (2),
2nd motor
Duration of 2nd segment of
acceleration, range is:
0.01 to 3600 sec.
10.00 sec A093 Deceleration time (2) 10.00 sec
A293 Deceleration time (2),
2nd motor
Duration of 2nd segment of
deceleration, range is:
0.01 to 3600 sec.
10.00 sec A094 Select method to switch to
Acc2/Dec2 profile
U 00 −
A294 Select method to switch to
Acc2/Dec2 profile, 2nd motor
Three options for switching from
1st to 2nd accel/decel:
00…2CH input from terminal
01…Transition frequency
02…Forward and reverse
U 00 −
A095 Acc1 to Acc2 frequency
transition point
U 0.0 Hz
A295 Acc1 to Acc2 frequency
transition point, 2nd motor
Output frequency at which
Accel1 switches to Accel2, range
is 0.0 to 400.0 Hz
U 0.0 Hz A096 Dec1 to Dec2 frequency
transition point
U 0.0 Hz A296 Dec1 to Dec2 frequency
transition point, 2nd motor
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 400.0 Hz
U 0.0 Hz A097 Acceleration curve selection Set the characteristic curve of
Acc1 and Acc2, five options:
00…linear
01…S-curve
02…U-curve
03…Inverse U-curve
04…EL S-curve
U 01 −
A098 Deceleration curve selection Set the characteristic curve of
Dec1 and Dec2, options are
same as above (a097)
U 01 −
A101 [OI] input active range start
frequency
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
U 0.00 Hz
A102 [OI] input active range end
frequency
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
U 0.0 Hz
A103 [OI] input active range start
current
The starting point (offset) for the
current input range,
range is 0. to 100.%
U 20. %
A104 [OI] input active range end
current
The ending point (offset) for the
current input range,
range is 0. to 100.%
U 100. %
A105 [OI] input start frequency
select
Two options; select codes:
00…Use offset (A101 value)
01…Use 0Hz
U 00 −