HP Integrity Superdome and 9000 Superdome sx2000 Electrical Specifications, IOX Cabinet Weights

Models: Integrity Superdome and 9000 Superdome sx2000

1 200
Download 200 pages 14.28 Kb
Page 50
Image 50

Table 2-3 System Component Weights (continued)

Component

Weight Per Unit

Quantity

Weight (lb/kg)

 

(lb/kg)

 

 

Cell power board

8.50/3.86

8

68.00/30.88

DIMMs

0.20/0.09

256

51.20/23.04

Bulk power supply

3.83/1.74

6

23.00/10.44

PDCA

26.00/11.80

2

52.00/23.59

I/O card cage

36.50/16.56

4

146.00/66.24

I/O cards

0.45/0.20

48

21.60/9.80

Fully configured server (SD32 cabinet)

 

1

1354.65/614.412

1The listed weight for a chassis includes the weight of all components not listed in Table 2-3.

2The listed weight for a fully configured cabinet includes all components and quantities listed in Table 2-3.

Table 2-4 IOX Cabinet Weights

Component

Weight1 (lb/kg)

Fully configured cabinet

1104.9/502.2

I/O card cage

36.50/16.56

Chassis

264/120

1The listed weight for a fully configured cabinet includes all items installed in a 1.6 meter cabinet. Add approximately 11 pounds when using a 1.9 meter cabinet.

Shipping Dimensions and Weights

Table 2-5lists the dimensions and weights of the SMS and a single cabinet with shipping pallet.

Table 2-5 Miscellaneous Dimensions and Weights

Equipment

Width (in/cm)

Depth/Length (in/cm)

Height (in/cm)

Weight (lb/kg)

System on shipping

39.00/99.06

48.63/123.5

73.25/186.7

1424.66/648.67

pallet123

 

 

 

 

Blowers and frame on

40.00/101.6

48.00/121.9

62.00/157.5

99.2/45.01

shipping pallet

 

 

 

 

IOX cabinet on shipping

38.00/96.52

48.00/121.9

88.25/224.1

1115/505.8

pallet 4

 

 

 

 

1Shipping box, pallet, ramp, and container add approximately 116 pounds (52.62 kg) to the total system weight.

2 Blowers and frame are shipped on a separate pallet.

3 Size and number of miscellaneous pallets are determined by the equipment ordered by the customer.

4 Assumes no I/O cards or cables installed. The shipping kit and pallet and all I/O cards add approximately 209 pounds (94.80 kg) to the total weight.

Electrical Specifications

The following specifications are based on ASHRAE Class 1. Class 1 is a controlled computer room environment, in which products are subject to controlled temperature and humidity extremes. Throughout this chapter each specification is defined as thoroughly as possible to ensure that all data is considered to ensure a successful site preparation and system installation.

50 System Specifications

Page 50
Image 50
HP Integrity Superdome and 9000 Superdome sx2000 manual Electrical Specifications, Shipping Dimensions and Weights