Table 2-8 Power Requirements (Without SMS) (continued)

Requirement

Value

Comments

Power factor correction

0.95 minimum

 

Ground leakage current (mA)

> 3.5 mA

See the following WARNING.

WARNING! Beware of shock hazard. When connecting or removing input power wiring, always connect the ground wire first and disconnect it last.

Component Power Requirements

Table 2-9 Component Power Requirements (Without SMS)

Component

Component Power Required 50 Hz to 60 Hz1

Maximum configuration for SD16

8,200 VA

Maximum configuration for SD32

12,196 VA

Cell board

900 VA

I/O card cage

500 VA

1A number to use for planning, to allow for enough power to upgrade through the life of the system.

IOX Cabinet Power Requirements

The IOX requires a single-phase 200-240 V ac input. Table 2-10lists the ac power requirements for the IOX cabinet.

NOTE: The IOX accommodates two ac inputs for redundancy.

Table 2-10 I/O Expansion Cabinet Power Requirements (Without SMS)

Requirement

Value

Nominal input voltage

200/208/220/230/240 V ac rms

Input voltage range (minimum to maximum)

170-264 V ac rms

Frequency range (minimum to maximum)

50/60 Hz

Number of phases

1

Marked electrical input current

16 A

Maximum inrush current

60 A (peak)

Power factor correction

0.95 minimum

Table 2-11 I/O Expansion Cabinet Component Power Requirements

Component

Component Power Required 50 Hz to 60 Hz

Fully configured cabinet

3200 VA

I/O card cage

500 VA

ICE

600 VA

IOX Cabinet Power Cords

Table 2-12lists the power cords for the IOX cabinet.