HP Integrity Superdome and 9000 Superdome sx2000 manual Acoustic Noise Specification, Airflow

Models: Integrity Superdome and 9000 Superdome sx2000

1 200
Download 200 pages 14.28 Kb
Page 56
Image 56

Table 2-16 HP Integrity Superdome/sx2000 Single-Core CPU Configurations (continued)

Cell (in cabinet)

Memory (DIMMs

I/O (fully

Typical Power

Cooling (BTU/Hr)

Breaker Power

 

per Cell)

populated)

(Watts)

 

(Watts)2

8

8

2

6823

23302

8596

8

4

4

7260

24794

9147

8

4

2

6300

21516

7938

6

16

4

6968

23797

8779

6

16

2

6008

20518

7570

6

8

4

6640

22677

8366

6

8

2

5680

19398

7156

6

4

4

6325

21601

7969

6

4

2

5365

18322

6759

4

16

4

5813

19852

7324

4

16

2

4853

16574

6114

4

8

4

4647

15870

5855

4

8

2

3687

12592

4645

4

4

4

5382

18380

6781

4

4

2

4422

15102

5571

2

16

2

3656

12486

4606

2

8

2

3534

12069

4453

2

4

2

3423

11690

4313

1Values in Table 2-15are based on 25 W load I/O cards, 1 GB DIMMs and four Intel® Itanium ® single-core processors

with 9 MB cache per cell board.

2These numbers are valid only for the specific configurations shown. Any upgrades can require a change to the breaker size. A 5-wire source uses a 4-pole breaker, and a 4-wire source uses a 3-pole breaker. The protective earth (PE) ground wire is not switched.

Acoustic Noise Specification

The acoustic noise specifications are as follows:

8.2 bel (sound power level)

65.1 dBA (sound pressure level at operator position)

These levels are appropriate for dedicated computer room environments, not office environments.

You must understand the acoustic noise specifications relative to operator positions within the computer room when adding HP Integrity Superdome/sx2000 systems to computer rooms with existing noise sources.

Airflow

HP Integrity Superdome/sx2000 systems require the cabinet air intake temperature to be between 15οC and 32οC (59οF and 89.6οF) at 2900 CFM.

Figure 2-2illustrates the location of the inlet and outlet air ducts on a single cabinet.

56 System Specifications

Page 56
Image 56
HP Integrity Superdome and 9000 Superdome sx2000 manual Acoustic Noise Specification, Airflow