cooling and electrical power. Table 2-15also lists the recommended breaker sizes for 4-wire and 5-wire sources.

WARNING! Do not connect a 380 to 415 V ac supply to a 4-wire PDCA. This is a safety hazard and results in damage to the product. Line-to-line or phase-to-phase voltage measured at 380 to 415 V ac must always be connected using a 5-wire PDCA.

Table 2-15 HP Integrity Superdome/sx2000 Dual-Core CPU Configurations1

Cells (in

Memory (DIMMs

I/O (fully

Typical Power

Cooling (BTU/Hr)

Breaker Power

cabinet)

per cell)

populated)

(Watts)

 

(Watts)2

8

32

4

9490

32382

11957

8

16

2

7620

26001

9601

8

8

4

8140

27776

10256

8

8

2

7180

24500

9047

8

4

4

7620

26001

9601

8

4

2

6660

22726

8391

6

16

4

7320

24978

9223

6

16

2

6360

21702

8013

6

8

4

7000

23886

8820

6

8

2

6040

20610

7610

6

4

4

6680

22794

8417

6

4

2

5720

19518

7207

4

16

4

6170

21054

7774

4

16

2

5210

17778

6564

4

8

4

5960

20337

7509

4

8

2

5000

17061

6300

4

4

4

5760

19655

7257

4

4

2

4800

16379

6048

2

16

2

4010

13683

5052

2

8

2

3890

13274

4901

2

4

2

3780

12898

4763

1Values in Table 2-15are based on 25 W load I/O cards, 1 GB DIMMs and four Intel® Itanium ® dual-core processors

with 18 MB or 24 MB cache per cell board or four PA-RISC processors with 64 MB.

2These numbers are valid only for the specific configurations shown. Any upgrades can require a change to the breaker size. A 5-wire source uses a 4-pole breaker, and a 4-wire source uses a 3-pole breaker. The protective earth (PE) ground wire is not switched.

Table 2-16 HP Integrity Superdome/sx2000 Single-Core CPU Configurations1

Cell (in cabinet)

Memory (DIMMs

I/O (fully

Typical Power

Cooling (BTU/Hr)

Breaker Power

 

per Cell)

populated)

(Watts)

 

(Watts)2

8

32

4

9130

31181

11503

8

16

2

7260

24794

9147

8

8

4

7783

26580

9806

Environmental Requirements

55

Page 55
Image 55
HP Integrity Superdome and 9000 Superdome sx2000 manual Cells Memory DIMMs Fully Typical Power Cooling BTU/Hr