HP Integrity Superdome and 9000 Superdome sx2000 manual Grounding, Circuit Breaker, Power Options

Models: Integrity Superdome and 9000 Superdome sx2000

1 200
Download 200 pages 14.28 Kb
Page 51
Image 51

Grounding

The site building must provide a safety ground or protective earth for each ac service entrance to all cabinets.

WARNING! This equipment is Class 1 and requires full implementation of the grounding scheme to all equipment connections. Failure to attach to protective earth results in loss of regulatory compliance and creates a possible safety hazard.

Circuit Breaker

Each cabinet using a 3-phase, 4-wire input requires a dedicated circuit breaker to support the Marked Electrical current of 44 A per phase. The facility electrician and local service codes determine proper circuit breaker selection.

Each cabinet using a 3-phase, 5-wire input requires a dedicated circuit breaker to support the Marked Electrical current of 24 A per phase. The facility electrician and local service codes determine proper circuit breaker selection.

NOTE: When using the minimum-size breaker, always choose circuit breakers with the maximum allowed trip delay to avoid nuisance tripping.

Power Options

Table 2-6describes the available power options. Table 2-7provides details about the available options. The options listed are consistent with options for earlier Superdome systems.

Table 2-6 Available Power Options

Option

Source

Source Voltage

PDCA

Input Current Per

Power Receptacle Required

 

Type

(Nominal)

Required

Phase 200 to 240 V

 

 

 

 

 

ac 1

 

6

3-phase

Voltage range 200 to 240

4-wire

44 A maximum per

Connector and plug provided

 

 

V ac, phase-to-phase, 50

 

phase

with a 2.5 meter (8.2 feet) power

 

 

Hz/60 Hz

 

 

cable. Electrician must hardwire

 

 

 

 

 

the receptacle to 60 A site power.

7

3-phase

Voltage range 200 to 240

5-wire

24 A maximum per

Connector and plug provided

 

 

V ac, phase-to-neutral,

 

phase

with a 2.5 meter (8.2 feet) power

 

 

50 Hz/60 Hz

 

 

cable. Electrician must hardwire

 

 

 

 

 

the receptacle to 32 A site power.

1A dedicated branch circuit is required for each PDCA installed.

Table 2-7 Option 6 and 7 Specifics

PDCA Part

Attached Power Cord

Attached Plug

Receptacle Required

Number

 

 

 

A5201-69023

OLFLEX 190 (PN 600804) is a 2.5 meter (8.2 feet)

Mennekes ME

Mennekes ME

(Option 6)

multiconductor, 600 V, 90˚ C, UL and CSA approved,

460P9 (60 A

460R9 (60 A

 

oil resistant flexible cable (8 AWG 60 A capacity).

capacity)

capacity)

A5201-69024

H07RN-F (OLFLEX PN 1600130) is a 2.5 meter (8.2 feet)

Mennekes ME

Mennekes ME

(Option 7)

heavy-duty neoprene-jacketed harmonized European

532P6-14 (32 A

532R6-1500 (32 A

 

flexible cable (4 mm2 32 A capacity).

capacity)

capacity)

Electrical Specifications

51

Page 51
Image 51
HP Integrity Superdome and 9000 Superdome sx2000 manual Grounding, Circuit Breaker, Available Power Options