Table 2-12 I/O Expansion Cabinet ac Power Cords

Part Number A5499AZ

Where Used

Connector Type

-001

North America

L6-20

-002

International

IEC 309

Environmental Requirements

This section provides the environmental, power dissipation, noise emission, and air flow specifications.

Temperature and Humidity Specifications

Table 2-13 Operational Physical Environment Requirements1

Temperature (Dry Bulb οC)2

Relative Humidity % Noncondensing

Dew Point3

Rate of Change (˚C/hr,

 

 

 

 

 

max)

Allowable4,5

Recommended6

Allowable5

Recommended6

 

 

15 to 32 (59ο to

20 to 25 (68ο to

20 to 80

40 to 55

17

5

90οF)

77οF)

 

 

 

 

1The maximum elevation for the operating environment is 3050 meters.

2Dry bulb temperature is the regular ambient temperature. Derate maximum dry bulb temperature 1˚C/300 m above 900 m.

3Must be a noncondensing environment.

4With installed media, the minimum temperature is 10˚C and maximum relative humidity is limited to 80%. Specific media requirements can vary.

5Allowable equipment design extremes as measured at the equipment inlet.

6 Recommended target facility design and operational range.

Table 2-14 Nonoperational Physical Environment Requirements

Storage

 

 

Powered Off (Installed)

 

Temp (˚C, dry

Rel Hum %;

Dew point

Temp (˚C, dry bulb

Rel Hum %

Dew point

bulb - regular

Noncondensing

(max)

- regular ambient

Noncondensing

(max)

ambient

 

 

temperature)

 

 

temperature)

 

 

 

 

 

-40 to 60

8 to 90

32

5 to 45

8 to 90

29

NOTE: The values in Table 2-14meet or exceed all ASHRAE specifications.

Power Dissipation

Table 2-15lists the power requirements by configuration (number of cell boards, amount of memory per cell, and number of I/O chassis) for the HP Integrity Superdome/sx2000.

The table contains two columns of power numbers expressed in watts. The Breaker Power column lists the power used to size the wall breaker at the installation site. The Typical Power column lists typical power. Typical power numbers can be used to assess the average utility cost of

54 System Specifications

Page 54
Image 54