Unpacking the PDCA

At least one PDCA ships with the system. In some cases, the customer might order two PDCAs, the second to be used as a backup power source. Unpack the PDCA and ensure it has the power cord option for installation.

Several power cord options are available for the PDCAs. Only options 6 and 7 are currently available in new system configurations (Table 3-1 (page 71)). Table 3-2 (page 71) details options 6 and 7.

Table 3-1 Available Power Options

Option

Source

Source Voltage

PDCA

Input Current Per

 

Type

(Nominal)

Required

Phase 200 to 240 V

 

 

 

 

ac1

6

3-phase

Voltage range 200 to

4-wire

44 A maximum per

 

 

240 V ac,

 

phase

 

 

phase-to-phase, 50 Hz

 

 

 

 

/ 60 Hz

 

 

7

3-phase

Voltage range 200 to

5-wire

24 A maximum per

 

 

240 V ac,

 

phase

 

 

phase-to-neutral, 50 Hz

 

 

 

 

/ 60 Hz

 

 

1A dedicated branch circuit is required for each PDCA installed.

Power Receptacle Required

Connector and plug provided with a 2.5 m (8.2 feet) power cable. An electrician must hardwire receptacle to 60 A site power.

Connector and plug provided with a 2.5 m (8.2 feet) power cable. An electrician must hardwire receptacle to 32 A site power.

Table 3-2 Power Cord Option 6 and 7 Details

PDCA Part Number

Attached Power Cord

Attached Plug

Receptacle Required

A5201-69023 (Option

OLFLEX 190 (PN 600804) is a 2.5 meter

Mennekes ME 460P9

Mennekes ME 460R9 (60

6)

multiconductor, 600 V, 90˚C, UL and CSA

(60 A capacity)

A capacity)

 

approved, oil resistant flexible cable. (8

 

 

 

AWG 60 A capacity)

 

 

A5201-69024 (Option

H07RN-F (OLFLEX PN 1600130) is a 2.5

Mennekes ME

Mennekes ME

7)

meter heavy-duty neoprene jacketed

532P6-14 (32 A

532R6-1500 (32 A

 

harmonized European flexible cable. (4

capacity)

capacity)

 

mm2 32 A capacity)

 

 

Returning Equipment

If the equipment is damaged, use the original packing material to repackage the cabinet for shipment. If the packing material is not available, contact the local HP Sales and Support Office regarding shipment.

Before shipping, place a tag on the container or equipment to identify the owner and the service to be performed. Include the equipment model number and the full serial number, if applicable. The model number and the full serial number are printed on the system information labels located at the bottom front of the cabinet.

WARNING! Do not attempt to push the loaded cabinet up the ramp onto the pallet. Three people are required to push the cabinet up the ramp and position it on the pallet. Inspect the condition of the loading and unloading ramp before use.

Repackaging

To repackage the cabinet, follow these steps:

1.Assemble the HP packing materials that came with the cabinet.

2.Carefully roll the cabinet up the ramp.

3.Attach the pallet mounting brackets to the pallet and the cabinet.

Unpacking and Inspecting the System

71

Page 71
Image 71
HP Integrity Superdome and 9000 Superdome sx2000 manual Unpacking the Pdca, Returning Equipment