Height

43 mm (1.7 in.)

 

 

Width

192 mm (7.5 in.)

 

 

Depth

221 mm (8.7 in.)

 

 

Weight

1.6 kg (3.5 lbs)

 

 

Operating temperatures

10° C–35° C (50° F–95° F) at 0–914 m (0–3000 ft)

 

10° C–32 ° C (50° F–90° F° ) at 914–2133 m (3000–7000 ft)

 

 

Operating humidity

8–80% (non-condensing)

 

 

Rated voltage

100–120 V ac, 30 A, single-phase

 

200–240 V ac, 30 A, single-phase

 

200–240 V ac, 32 A, single-phase

 

200–240 V ac, 30 A, single-phase

 

380–415 V ac, 32 A, single-phase

 

 

Rated frequency

50–60 Hz

 

 

Maximum power rating

4800-6000 VA

 

 

Power inlet

One fixed line cord

 

 

Power outlets

Three IEC 320-C19 outlets rated at 16 A (VDE) / 20 A

 

(UL/CSA)

 

 

Line cords

The 2.5 m (8.2 ft) fixed line cord on the Rack PDU determines the connectivity of the Rack PDU. The following table contains a list of the line cords that you can use with the Rack PDU:

Power Source

Line cord rating

Plug type

Line cord

part #

 

 

 

 

 

 

 

100-127 V ac, 30 A, single-phase

127 V, 30 A

NEMA L5-30P

24P6846

 

 

 

 

200-240 V ac, 30 A, single-phase

250 V, 30 A

NEMA L6-30P

24P6847

 

 

 

 

200-240 V ac, 32 A, single-phase

250 V, 32 A

IEC 309-2P + Gnd

24P6848

 

 

 

 

200-240 V ac, 30 A, three-phase

250 V, 30 A

NEMA L21-30P

24P6844

 

 

 

 

380-415 V ac, 32 A, three-phase

415 V, 32 A

IEC 309-3P + N + Gnd

24P6845

 

 

 

 

Power cables

The Rack PDU comes with three power cables, that you use to connect to other M/PDU family devices, as listed in the following table:

NetBAY Power Distribution Units 165

Page 173
Image 173
IBM 4SB, 9TX, 9TS, 9QX, 9QS, 900, 4SA, 42P, 42X, 200, 42E, 42S, 4QS, 4QX manual Line cords, Power cables