Unsupervised Alarm Input Configuration and Wiring

Unsupervised relay contacts are not terminated. They are wired as either normally open or normally closed. Set switch 1 down. Set switch 2 up for normally closed (N.C.) or down for normally open (N.O.). Refer to Figure 6.

Unsupervised modes are easily defeated and should not be used in critical situations when security is most important.

SWITCH SETTINGS UNSUPERVISED, NORMALLY CLOSED (NTSC)

1 2 3 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NTSC/PAL

 

 

NOT USED

 

 

SWITCH SETTINGS

UNSUPERVISED, NORMALLY

OPEN (NTSC)

1 2 3 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NTSC/PAL

 

 

 

 

NOT USED

 

 

 

UNSUPERVISED MODE CONSIDERATIONS INDIVIDUAL ALARM WIRING CONDITIONS

NO ALARM

NORMALLY CLOSED

+V

ALM

UNIT

GND

NO ALARM

NORMALLY OPEN

+V

ALM

UNIT

GND

NORMAL

ALARM CONDITION

+V

ALM

UNIT

GND

NORMAL

ALARM CONDITION

+V

ALM

UNIT

GND

ALARM CONDITION

+V

ALM

UNIT

GND

CUT WIRE

NO ALARM CONDITION

+V

ALM

UNIT

GND

CUT WIRE

NEVER WILL BE AN

ALARM CONDITION HERE

UNSUPERVISED GROUP ALARM WIRING CONDITIONS

UNSUPERVISED, NORMALLY OPEN

1

2

3

4

5

6

7

8

UNSUPERVISED, NORMALLY CLOSED

1

2

3

4

5

6

7

8

Figure 6. Unsupervised Alarm Input Wiring