Commissioning
9.2 Procedure
3. Select the motor
Before the motor is selected, message 300701 "Commissioning required" must appear; see screenshot below.
a) The torque motor appears in the list → Select the motor
Figure 9-3 Selection of a motor for which data has already been defined
b) The torque motor does not appear in the list
→ Select "NonSiemens mot.", enter the relevant data in the "Motor" field
Note
If a lower identification current is required (< 40%), bit 5 should be used to hide alarm 300753 in MD 1012.
172 | 1FW6 |
Configuration Manual, 05/2009, |