Siemens 611 Select the motor, Selection of a motor for which data has already been defined

Models: 611

1 324
Download 324 pages 4.89 Kb
Page 172
Image 172

Commissioning

9.2 Procedure

3. Select the motor

Before the motor is selected, message 300701 "Commissioning required" must appear; see screenshot below.

a) The torque motor appears in the list → Select the motor

Figure 9-3 Selection of a motor for which data has already been defined

b) The torque motor does not appear in the list

→ Select "NonSiemens mot.", enter the relevant data in the "Motor" field

Note

If a lower identification current is required (< 40%), bit 5 should be used to hide alarm 300753 in MD 1012.

172

1FW6 Built-in torque motors

Configuration Manual, 05/2009, 6SN1197-0AD00-0BP7

Page 172
Image 172
Siemens 611 configurationmanual Select the motor, Selection of a motor for which data has already been defined