Technical Specifications

B.1 Technical Specifications of the SIMATIC Box PC 620

General

 

Order nos.

See order documentation

Dimensions (w x h x d)

295x265x80 mm, without CD-ROM drive

 

295x265x100 mm, with CD-ROM drive

Weight

approx. 6kg (13.5 lbs.)

Supply voltage (UN)

120 V (85 V to 132 V (AC),

 

or 230 V (170 V to 265 V) AC (autorange)

 

alternative: 24 V (20.4 bis 28.8 V) DC, SELV

Line voltage frequency, AC

50/60 Hz (47 to 63 Hz)

 

 

Brief voltage interruption acc. to Namur

max. 20 ms at 0.85 UN

 

(max. 10 times per hour; min. recovery time 1 s)

max. power consumption for 85W power supply

120W

 

 

max. power consumption for 105W power

132W

supply

 

 

 

max. current output (DC), according to form of

+5V/ 10A or 13.5A

power supply

3,3V/4.2A or 8.5A

 

 

+12V/1.7 A or 2.5A

 

–12/0.2A or 0.3A (in total max. 85W or 105W)

 

 

Noise emission

< 55dB(A) to DIN 45635

Enclosure

IP20

Safety

 

 

 

Protection class

Protection class I pursuant IEC 60536

 

 

Safety specifications with AC power supply

UL1950/IEC 60950 corresponds to DIN VDE 0805

 

 

Safety specifications with DC power supply

UL508

 

 

Electromagnetic compatibility (EMC)

 

Emitted interference with power supply 105W

EN 55022 Class A (requirement for industrial sector) for devices with AC power supply EN6100-3-2 class D and EN61000-3-3

Emitted interference with power supply 85W

EN 55022 Class B (requirement for domestic and

 

industrial sector)

 

 

for devices with AC power supply EN6100-3-2 class D

 

and EN61000-3-3

 

 

 

 

Noise immunity:

±.2 kV

(to IEC 61000-4-4; Burst)

Mains borne disturbance variables on supply

± 1 kV

(to IEC 61000-4-5; Surge symm)

lines

± 2 kV

(to IEC 61000-4-5; Surge unsymm)

 

 

 

 

Noise immunity on signal lines

± 1 kV

(IEC 61000-4-4; Burst; length < 5 m)

 

± 2 kV

(IEC 61000-4-4; Burst; length > 5 m)

 

± 2 kV

(to IEC 61000-4-4:1995; Surge unsymm;

 

 

length > 30 m)

 

 

 

 

Noise immunity to discharges of static electricity

± 6 kV Contact discharge

(to IEC 61000-4-2)

 

± 8 kV Air discharge

(to IEC 61000-4-2)

 

 

Immunity to RF interference

10 V/m 80-1000 MHz, 80% AM (to IEC 61000-4-3)

 

10 V/m 900 MHz and 1,89 GHz, 50% ED

 

(to IEC 61000-4-3)

 

 

10 V 9KHz- 80MHz

(to IEC 61000-4-6)

 

 

 

Magnetic field

30 A/m 50Hz

(to IEC 61000-4-8)

B-2

SIMATIC Box PC 620 Manual

A5E00131465-01

Page 188
Image 188
Siemens 620 appendix Technical Specifications of the Simatic Box PC, General, Safety, Electromagnetic compatibility EMC