Panel Calibration

Panel Calibration

This section outlines the steps for calibrating the touch panel. Calibrating the panel before its initial use and after completing a firmware download is highly recommended.

Modero panels are set up in the factory with specific demo touch panel pages. The first splash screen that appears indicates the panel is receiving power, beginning to load firmware, and preparing to display the default touch panel pages. When the panel is ready, the AMX Splash Screen is replaced by the Initial Panel Page.

Calibrating the Modero Panel

1.Press and hold the grey Front Bezel button (FIG. 15) for 8 seconds to pass over the Setup page and access the Calibration setup page (FIG. 16).

Front Bezel button

4 second press/hold:

Opens the Setup page

6 second press/hold:

Opens the Calibration page

Single press puts the panel to sleep

FIG. 15 Location of Front Setup Access button

2.Press the crosshairs (on the Calibration page) to set the calibration points on the LCD (FIG. 16).

The request to touch the crosshairs is the first on-screen message

Calibration successful is the second on-screen message that appears after the calibration process is completed

On-screen crosshairs used for

calibration of the touch device

FIG. 16 Touch Panel Calibration Screens

3.After the "Calibration Successful." message appears, press anywhere on the screen to continue and return to the Setup page.