AMX NXD-500i manual Calibration Page, Calibration page actually 3 separate screens

Models: NXD-500i

1 148
Download 148 pages 52.91 Kb
Page 67
Image 67
Calibration Page

Setup Pages and Descriptions

Calibration Page

The Calibration page (FIG. 46) allows you to calibrate the touch panel for maximum sensitivity. Press and hold the Front Setup Access button for 6 seconds to access the Calibration page. Press the crosshairs to calibrate the panel and return to the last active firmware page.

The request to touch the crosshairs is the first on-screen message

Calibration successful is the second on-screen message that appears after the calibration process is completed

On-screen crosshairs used for calibration of the touch device

FIG. 46 Calibration page (actually 3 separate screens)

If the calibration was improperly set and the Calibration page cannot be reached through the panel’s firmware, this firmware page may be accessed via G4 Web Control. Navigate to the Protected Setup page and press the Calibrate button through the VNC window. This action causes the panel to go to the Calibration page seen above, where the touch panel may be physically recalibrated again using the above procedures.

NXD-500i 5" Wall/Flush Mount Touch Panel with Intercom

61

 

 

Page 67
Image 67
AMX NXD-500i manual Calibration Page, Calibration page actually 3 separate screens