Upgrading Modero Firmware

6.From within Studio, select Tools > Firmware Transfers > Send to NetLinx Device from the Main menu to open the Send to NetLinx Device dialog (B in FIG. 34). Verify the panel’s System and Device number values match those values listed within the System folder in the OnLine Tree tab of the Workspace window (A in FIG. 34).

A

B

FIG. 34 Using USB for a Virtual Master transfer

7.Select the panel’s Kit file from the Files section.

8.Enter the Device value associated with the panel and the System number associated with the Master listed in the OnLine Tree tab of the Workspace window. The Port field is greyed-out.

9.Click the Reboot Device checkbox. This causes the touch panel to reboot after the firmware update process is complete. The reboot of the panel can take up 30 seconds after the firmware process has finished.

10.Click Send to begin the transfer. The file transfer progress is indicated on the bottom-right of the dialog (B in FIG. 34).

11.As the panel is rebooting, temporarily unplug the USB connector on the panel until the panel has completely restarted.

12.Once the first panel page has been displayed, reconnect the USB connector to the panel.

13.Right-click the associated System number and select Refresh System. This causes a refresh of all project systems, establishes a new connection to the Master, and populates the System list with devices on your particular system.

14.Confirm that the panel has been properly updated to the correct firmware version.

46

NXD-500i 5" Wall/Flush Mount Touch Panel with Intercom

Page 52
Image 52
AMX NXD-500i manual Using USB for a Virtual Master transfer