Problem

Check

 

 

The CAN2 LED is flashing

The CAN bus is passive. This means that the bus is operational but

red.

errors are occurring.

 

Check that all nodes are running at the same baud rate.

 

Check that each node has been assigned a unique NodeID.

 

Check that the network has been terminated at each end. If the

 

MintDrive is at the end of the network, check that the CAN2 switch on

 

the front panel is in the ON position.

 

Check that the jumpers on each CAN peripheral are in the correct

 

position. JP1 and JP2 should be set for bus 2 (see page 120).

 

Check the CAN cable.

 

Check for sources of errors on the bus.

 

Type CANBUSRESET to reset the bus.

 

 