Code

Problem

Check

 

 

 

12

Over voltage fault

Bus over voltage condition occurred.

 

 

If this occurs during high deceleration, a regeneration resistor

 

 

might need to be installed. If a regeneration resistor is already

 

 

installed check the wiring and if it has an adequate rating.

 

 

Alternatively, try decreasing the Mint DECEL parameter.

 

 

Check that the correct AC voltage is being supplied for the power

 

 

rating of your MintDrive.

 

 

Check for power input line disturbances (mains spikes) and fit a

 

 

mains filter.

 

 

Measure the actual input voltage being supplied to the MintDrive

 

 

and check that it is within the specification.

 

 

If the problem persists, contact Baldor Technical Support.

 

 

 

15

Under voltage fault

DC Bus Voltage has fallen below minimum threshold.

 

 

If this occurs during acceleration then the load may be too great for

 

 

the acceleration selected. Try reducing the value of the Mint ACCEL

 

 

parameter.

 

 

Check that the correct AC voltage is being supplied for the power

 

 

rating of your MintDrive.

 

 

If the fault occurs immediately after power-up, remove the

 

 

regeneration resistor (if connected) and try again.

 

 

Check for power input line disturbances (sags caused by start-up

 

 

of other equipment).

 

 

Measure the actual input voltage being supplied to the MintDrive

 

 

and check that it is within the specification

 

 

If the problem persists, contact Baldor Technical Support.

 

 

 

16

Overload

The current rating of the drive has been exceeded.

 

 

Check the motor and feedback wiring.

 

 

If this occurs·during high acceleration rates, decrease the Mint

 

 

ACCEL parameter and/or reduce the motor load.

 

 

Check the motor and load for excessive friction or improper

 

 

operation such as a broken gear in a gearbox.

 

 

 