2.3.4Wire sizes

Input and output wire size is based on the use of copper conductor wire rated at 167°F (75°C). The following tables describe the wire size to be used for power connections and the ratings of the protection devices.

Catalog Number

 

 

Incoming Power

 

 

 

 

 

D-Type

Input

Wire Gauge

 

Nominal

Continuous

Fuse

 

 

 

 

Input

Output

Input

Time

 

 

 

Breaker

AWG

mm2

 

Voltage

Amps (RMS)

(A)

Delay

 

 

 

(A)

 

 

MD1A02xx-xxxx

115V (1φ)

2.5A

6

6

14

2.5

MD2A02xx-xxxx

230V (1φ)

2.5A

6

6

14

2.5

MD1A05xx-xxxx

115V (1φ)

5A

10

10

14

2.5

MD2A05xx-xxxx

230V (1φ)

5A

10

10

14

2.5

MD1A07xx-xxxx

115V (1φ)

7.5A

16

16

14

2.5

MD2A07xx-xxxx

230V (1φ)

7.5A

16

16

14

2.5

MD1A10xx-xxxx

115V (1φ)

10A

20

20

14

2.5

MD2A10xx-xxxx

230V (3φ)

10A

20

20

14

2.5

MD1A15xx-xxxx

115V (1φ)

15A

32

32

12

2.5

MD2A15xx-xxxx

230V (3φ)

15A

32

32

12

2.5

Note: All wire sizes are based on 75°C copper wire. Higher temperature smaller gauge wire may be used per NEC and local codes. Recommended fuses/breakers are based on 77°F (25°C) ambient, maximum continuous control output current and no harmonic current.