The inputs are conditioned using low pass RC filters and Schmitt trigger buffers. If an input is configured as edge triggered, the triggering pulse must have a duration of at least 1ms (one software scan) to guarantee acceptance by MintMT. Voltages below 2V are considered as 0V. The use of shielded cable for inputs is recommended.

Active high: The digital inputs will be active when a voltage of +24VDC (±20%) is applied to them and will sink a maximum of 8mA each.

Active low: The digital inputs will be active when grounded (<2V) and will source a maximum of 8mA each.

Note: Sustained input voltages above 28V will damage the inputs.

4.4.2 Digital inputs - X2

12

Location

Breakout module, connector X2

 

 

 

 

 

 

 

Pin

Name

MintMT keyword /

Common

 

 

 

description

 

 

 

 

 

 

 

1

Shield

Shield connection

 

 

 

 

 

 

 

2

DIN4

INX.4

 

1

 

 

 

 

3

DIN5

INX.5

Common1

 

 

 

 

 

4

DIN6

INX.6

 

 

 

 

 

 

 

 

5

DIN7

INX.7

 

 

 

 

 

 

 

6

DIN8

INX.8

 

 

 

 

 

 

 

7

DIN9

INX.9

Common2

 

 

 

 

 

8

DIN10

INX.10

 

 

 

 

 

 

 

 

9

DIN11

INX.11

 

 

 

 

 

 

 

10

Shield

Shield connection

 

 

 

 

 

 

 

11

Common1

Common connection

 

 

 

 

 

 

 

12

Common2

Common connection

 

 

 

 

 

 

 

Description

 

 

 

 

Eight general purpose optically isolated AC digital inputs.

 

 

 

 

 

 

The inputs are electrically identical to inputs DIN12 to DIN19 described in section 4.4.1.

MN1903

Input / Output 4-11

Page 27
Image 27
Baldor MN1903 installation manual INX.4