Fujitsu BX600 S2 manual Notes on Safety, Before Setting Up V CAUTION

Models: BX600 S2

1 173
Download 173 pages 6.42 Kb
Page 22
Image 22
Notes on Safety

Notes on Safety

Important Notes

Before Setting Up

VCAUTION!

During installation and before operating the device, observe the instructions on environmental conditions for your device in the section “Technical Data” on page 15.

If the device is brought in from a cold environment, condensation may form on both the inside and outside of the machine.

Before operating the device, wait until it is absolutely dry and has reached approximately the same temperature as the installation site. Failure to observe these guidelines can lead to physical damage of the device.

Transport the device only in the original packaging or in packaging which protects it from knocks and jolts.

Installation and Operation

VCAUTION!

For safety reasons, make sure you read any warning labels when removing modules from the server.

Beware of energy hazards on the plug-in contacts of the midplane. A short circuit on these connections can lead to damage to the system.

PRIMERGY BX620 S4 server blades are not for use in slots 4 an 10 of the PRIMERGY BX600 S2 basic unit.

If the server is integrated in a (rack) installation that receives power from an industrial (public) power supply network with the IEC309 connector, the (public) power supply protection must comply with the requirements for the non-industrial (public) power supply networks for the type-A connector.

For the PRIMERGY BX600 S2 basic unit only 2100W PSUs are allowed (Product no. A3C40073262)! The 1200W PSUs of the PRIMERGY BX600 S1 basic unit is not allowed for the PRIMERGY BX600 S2 basic unit.

The 2100W PSU is not allowed for the PRIMERGY BX600 S1 basic unit.

22

PRIMERGY BX600 S2 Basic Unit

Page 22
Image 22
Fujitsu BX600 S2 manual Notes on Safety, Before Setting Up V CAUTION, Installation and Operation V CAUTION