3.6Notes on Installing in the Rack
VCAUTION!
●For safety reasons, at least two people are needed to install the basic unit because of its weight and size.
●For lifting the basic unit, use the handles on the front and the
●Before lifting the basic unit into the rack, remove server blades, fan units and power supplies from the system unit to reduce weight.
●For lifting the basic unit, use the handles on the front and the
●Never lift or transport the server using the handles on the rear.
●For safety reasons only one unit may be withdrawn from the rack at a time when performing assembly or service work.
●Ensure that the
●If more than one unit is withdrawn from the rack at any one time, the rack is in danger of tilting forward.
●When connecting and disconnecting cables, read the relevant notes in the “Important notes” chapter in the technical manual for the relevant rack. The technical manual is supplied with the corre- sponding rack.
●The power connection for the rack must be installed by an authorized technician (electrician).
●If the server is integrated in a (rack) installation that receives power from an industrial (public) power supply network with the IEC309 connector, the (public) power supply protection must comply with the requirements for the
●The power supply for the rack should be divided amongst the three phases of a