Trap overview

Trap name

ID

Meaning

Error class

 

 

 

 

softwareBypass

21

The UPS has been set to

minor

 

 

bypass by a user via software

 

 

 

or via the UPS front panel.

 

 

 

 

 

switchedBypass

22

The UPS has been set to

minor

 

 

bypass by a user via the switch

 

 

 

on the back.

 

 

 

 

 

upsBatteryNeeds

17

The UPS batteries require

major

Replacement

 

immediate replacement.

 

 

 

 

 

upsDiagnosticsFailed

3

Internal UPS self-test failed.

major

 

 

 

 

upsDiagnosticsPassed

10

Internal UPS self-test passed.

informational

 

 

 

 

upsDipSwitchChanged

16

The UPS DIP switch settings

minor

 

 

have been changed.

 

 

 

 

 

upsDischarged

4

The UPS batteries are

major

 

 

discharged. If utility power fails

 

 

 

an immediate low battery

 

 

 

condition will exist. Sufficient

 

 

 

runtime for necessary action

 

 

 

cannot be guaranteed.

 

 

 

 

 

upsOnBattery

5

The UPS is now providing

minor

 

 

battery backup power.

 

 

 

 

 

upsOverload

2

The UPS has sensed a load

major

 

 

greater than 100% of its rated

 

 

 

capacity.

 

 

 

 

 

upsRebootStarted

15

The UPS has started the

minor

 

 

reboot sequence. The UPS will

 

 

 

reboot itself at this time.

 

 

 

 

 

upsSleeping

13

The UPS is entering sleep

minor

 

 

mode.

 

 

 

 

 

upsTurnedOff

12

The UPS has been switched off

minor

 

 

by a management station.

 

 

 

 

 

upsTurnedOn

30

The UPS is turned on.

informational

 

 

 

 

upsWokeUp

14

The UPS has woken up from

informational

 

 

sleep mode. Power to the load

 

 

 

has been restored.

 

 

 

 

 