Chapter 10 - Create/Edit

Notification Class

To change the order of the columns, click and hold the column and move it to the desired location within the table.

Using the Notification Class Editor

If a Remote Destination is added to a Notification Class object, all recipients in the Remote Destinations table will receive an e-mail notification of the alarm condition.

Notification will come from the Sender’s E-mail Address field as configured in the SMTP Configuration Editor. The e-mail notification will indicate the time local to the field panel, as well as the field panel name, point system name, point descriptor, “to” state, event value, and priority:

From: MichaelS@fwrd.rd.net [mailto:MichaelS@fwrd.rd.net]

Sent: Friday, September 09, 2011 4:29 AM

To: Smith, Michael

Subject: Building Automation Alarm Notification

Field panel name :EPXCM80

Time Stamp :09:29:17 SEP-09-2011 FRI

Point system name :mm

Point Descriptor :

To State :*A1*unACK

Event Value : 100.0

Priority :BN08

Creating a Notification Class Object

1.

Click the Notification Class icon from the Create/Edit bar.

 

The Notification ClassEditor window displays.

2.

Click Select a Panel at the top of the left pane of the Notification Class Editor

 

window to display available panels.

3.

Select the desired panel by clicking the panel name in the left pane of the

 

Notification Class Editor window.

4.

Click the + button at the bottom left of the Notification Class Editor window.

 

The Notification Class Editor window displays a new Notification Class object.

5.

Enter the new Notification Class object information.

6.

To add a network destination, click the + button at the bottom left of the Network

 

Destinations table.

 

- In the Process ID cell, enter the process ID. The default value is 600.

 

- In the Recipient cell, enter the recipient via the drop-down choices.

 

- In the Valid Days cell, choose the valid days by checking the desired

 

checkboxes.

 

- In the From Time-To Time cell, enter the desired times.

102

 

 

Siemens Industry, Inc.

 

125-3584T

Page 102
Image 102
Siemens 125-3584T manual Using the Notification Class Editor, Creating a Notification Class Object