Chapter 11 - FINlite Graphics Tool

Using the FINlite Graphics Tool

In the Field Panel Web Server User Interface

To apply the relativized graphics file to an FLN device:

1.Open the relativized graphics file.

Device Template graphics (relativized graphics files) are stored within the selected panel in the Graphics area, by application ID (Graphics\Application\ApplicationID).

Because Device Template graphics are published to the Graphics\Application\AppID folder on the panel, rather than in the Graphics folder, they cannot be used as default graphics.

-A Select Device drop-down list will display in the Graphics Viewer on the right side of the Web Server.

2.Select the device whose live data should display in the relativized graphic.

3.Click Go.

The relativized graphic will display the live data from the selected device.

Backing Up Graphics

Use this procedure to back up graphics files via the HMI.

HMI

S, H, E, W, G (System, Hardware, Ethernet, Webserver, Graphicsbackup

 

Example

 

10:13:04 07/30/2010 FRI Logged on successfully Field panel

 

<40091>

 

 

User: <high> <High default user account>

 

>Point, Application, Time, Message, Cancel, System, passWord,

 

Bye? s

 

>Diagnostics, Users, dSt, Bacnet, Error_msgs, Hardware, Text,

 

Quit? h

 

>Fieldpanels, Ethernet, nodeNametable, Disks, Reportprinter,

 

Licensemanager, Quit? e

 

155

Siemens Industry, Inc.

 

125-3584T

Page 155
Image 155
Siemens 125-3584T manual Backing Up Graphics, Field Panel Web Server User Interface