Chapter 10 - Create/Edit

Point

3.Select the desired panel by clicking the panel name in the left pane of the Point Editor window.

4.Either select an existing point or create a new point by clicking the + button at the bottom left of the Point Editor window.

The point information window will open, displaying point information.

5.Check the Alarmable checkbox to create an Intrinsic Alarm. Enter related information (see the User Interface Description for the Point Editor Application section for more information about related fields).

6.Click Save.

The Save button will be grayed out once the modifications are complete.

Modifying a Point

1.Select the Point icon from the Create/Edit bar.

The Point Editor window will open.

2.Click “Select a Panel” at the top of the left pane of the Point Editor window to display available panels.

3.Select the desired panel and the desired point by clicking the panel name and then the point name.

The point information window will open, displaying point details.

4.Make the desired modifications to the existing point.

5.Click Save.

The Save button will be grayed out once the modifications are complete.

 

71

Siemens Industry, Inc.

125-3584T

Page 71
Image 71
Siemens 125-3584T manual Modifying a Point