The Time Delay field allows you to specify the time (in seconds) that the object must be in or out of alarm or fault for a notification to be sent.

The Notification Class dropdown allows you to choose the notification class that the Event Enrollment Object will use. If no Notification Class is specified, no panels will be notified.

Type-specific Parameters:

The States list displays the available alarm values. This parameter applies to COS Event Enrollment Object types only.

The Feedback Point dropdown provides the object reference for the feedback from the object to be monitored. This parameter is required for creating an Event Enrollment Object and cannot be edited. This parameter applies to FAL Event Enrollment Object types only.

The Set Point dropdown provides the object reference for the setpoint. This parameter is required for creating an Event Enrollment Object and cannot be edited. This parameter applies to LIM and OOR Event Enrollment Object types only.

The High Diff Limit and Low Diff Limit fields allow you to set the differential limit from the setpoint. These parameters apply to LIM Event Enrollment Object types only.

The High Limit and Low Limit fields allow you to set object’s high and low limit alarm values. These parameters apply to OOR Event Enrollment Object types only.

The Deadband field allows you to set the deadband value to determine normal alarm parameters. This parameter applies to LIM and OOR Event Enrollment Object types only.

Tips for Using the Event Enrollment Editor

If the Event Enrollment object is not configured as alarmable, it will not be counted in fault counts even if the object is in fault status.

Using the Event Enrollment Editor

Creating an Event Enrollment Object

1.Click the Event Enrollment icon from the Create/Edit bar. The Event EnrollmentEditor window displays.

2.Click Select a Panel at the top of the left pane of the Event EnrollmentEditor window to display available panels.

3.Select the desired panel by clicking the panel name in the left pane of the Event EnrollmentEditor window.

4.Click the + button at the bottom left of the Event EnrollmentEditor window.

 

95