Chapter 12 - Field Panel Features for Field Panel Web Server

Backing up and Restoring Databases

When Web Server is enabled on a panel, Auto Save and Auto Restore are enabled as the default. You can manually disable them using the HMI.

If you are using TALON View as a mass storage device, do not enable Auto Restore in Web Server. If Auto Restore is already enabled, it must be manually disabled.

For more information, see the Enabling Auto Save section and TALON Controllers User's Manual (588-580).

Graphics files cannot be backed up using the Auto Save feature. For information about backing up graphics files, see the Saving and Publishing the Graphics File section.

Enabling Auto Save

To enable the Auto Save feature via the HMI.

HMI

S, H, F, C, L, U (System, Hardware, Fieldpanels, Config, db_fiLe, aUtosave)

Prompt/Field Entry

Option

Description

 

 

 

Enable, Disable, Quit?

E, D, Q

 

 

 

 

Field panel name

 

Alphanumeric value, 30 character limit

 

 

 

Are you sure (Y/N)

Y

 

 

 

 

Auto Save Enabled or Auto Save Disabled will display.

Example

>Point, Application, Time, Message, Cancel, System, passWord, Bye? s

>Diagnostics, Users, dSt, Bacnet, Error_msgs, Hardware, Text, Quit? h

>Fieldpanels, Ethernet, nodeNametable, Disks, Reportprinter, Licensemanager, Quit? f

>Log, Display, Add, dElete, Modify, Config, Filesys, Quit? c >Hmi, Aln, deVice, Names, Fln, nEttype, Defaultlanguage, db_fiLe, Quit? l

>Save, Clear, Restore_db, Autorestore, aUtosave, Display, Quit?

u

 

 

>Enable, Disable, Quit? e

:

-------

>Field panel

>Are you sure (Y/N)

:

y

Field panel 130: Auto Save Enabled

 

169

Siemens Industry, Inc.

125-3584T

Page 169
Image 169
Siemens 125-3584T manual Enabling Auto Save, To enable the Auto Save feature via the HMI