Chapter 10 - Create/Edit

Event Enrollment

The Object Name field allows you to name the Event Enrollment Object using up to 30 characters. This field is required for creating an Event Enrollment Object and cannot be edited in an existing object.

The Object Identifier field displays the point Object Identifier information. An Object Identifier consists of an object type and instance number. The object type is the BACnet standard object type enumeration value (Event Enrollment object type enumeration value is 9). You can enter an instance number on point creation in this field, or leave it blank. If you do not enter an instance number in the Object Identifier field on creation, the controller will automatically enter the next available instance number. After creation, the Object Identifier field cannot be edited and the field will show the object type and instance number separated by commas.

The Description field allows you to describe the Event Enrollment Object using up to 16 alphanumeric characters. This field is optional for creating an Event Enrollment Object and can be edited.

The event type options allow you to choose the Event Enrollment Object type:

COS - Change of State (for BI, BV, MI, and MV point types)

FAL - Command Failure (for BO and MO point types)

LIM - Floating Limit (for AO and AV point types)

OOR - Out of Range (for AI, AO, and AV point types)

The OFFNORMAL, NORMAL, and FAULT Alarm Enabled checkboxes allow you to define which transitions will be reported. These parameters are optional for Event Enrollment Object creation and can be edited.

The Notify Type dropdown allows you to choose “alarm” or “event” type of notification.

The Reference Point field allows you to choose the object reference for the object to be monitored. This parameter is required for Event Enrollment Object creation and cannot be edited.