Chapter 10 - Create/Edit
Event Enrollment
94
Siemens Industry, Inc. 125-3584T
The Object Name field allows you to name the Event Enrollment Object using up to
30 characters. This field is required for creating an Event Enrollment Object and
cannot be edited in an existing object.
The Object Identifier field displays the point Object Identifier information. An Object
Identifier consists of an object type and instance number. The object type is the
BACnet standard object type enumeration value (Event Enrollment object type
enumeration value is 9). You can enter an instance number on point creation in this
field, or leave it blank. If you do not enter an instance number in the Object
Identifier field on creation, the controller will automatically enter the next available
instance number. After creation, the Object Identifier field cannot be edited and the
field will show the object type and instance number separated by commas.
The Description field allows you to describe the Event Enrollment Object using up
to 16 alphanumeric characters. This field is optional for creating an Event
Enrollment Object and can be edited.
The event type options allow you to choose the Event Enrollment Object type:
COS - Change of State (for BI, BV, MI, a nd MV point types)
FAL - Command Failure (for BO and MO point types)
LIM - Floating Limit (for AO and AV point types)
OOR - Out of Range (for AI, AO, and AV point types)
The OFFNORMAL, NORMAL, and FAULT Alarm Enabled checkboxes allow you to
define which transitions will be reported. These parameters are optional for Event
Enrollment Object creation and can be edited.
The Notify Type dropdown allows you to choose “alarm” or “event” type of
notification.
The Reference Point field allows you to choose the object reference for the object
to be monitored. This parameter is required for Event Enrollment Object creation
and cannot be edited.