Chapter 13 - Troubleshooting

Graphics Issues

 

panels lose communication, an error message will display for each panel, indicating

 

which panel has lost communication.

 

If an FPWeb-enabled panel loses communication, the Device Failures Count will

 

increase, and the Panel will have an associated triangle icon in the navigation pane

 

instead of an arrow.

 

Solution: Check connections. Verify the panel is still FPWeb-enabled. Communications

 

should be reestablished automatically as long as the browser session has not been

 

terminated.

 

Graphics Issues

 

Displaying New Graphics in Browser

 

Issue: The Web browser displays an older graphics file, even after the file has been

 

modified and saved.

 

Solution: Internet Explorer and Firefox store Web pages and flash files as “temporary

 

Internet files” for faster loading. Clear the cache by deleting temporary Internet files

 

(see browser Help system for more information). This should allow the application to

 

display the newest graphics files.

 

Existing Images are Resized after New Animation Frames are Added

 

Issue: After a new animation image has been added to the set of frames in FINlite’s

 

Animation Editor window, existing images are automatically resized to match the frame

 

added by the user.

 

Solution: Before bringing them into FINlite, be sure the images to be added for editing

 

animation are sized similarly to the existing images, to avoid automatic resizing issues.

 

User is Unable to Log in to Panel via FINlite

 

Issue: If you open a graphic from your local file system before you have logged into

 

any panels and then select Enter Live Mode, FINlite will display an error message.

 

When you click OK, the login screen will display. The Panel Address will be populated

 

with the last address that was used for login. If this is the first login of the current

 

FINlite session, then the URL of the first bound point in the graphic is used. The Panel

 

Address field is grayed out. If this is not the desired panel or if this panel is currently

 

failed or unavailable, you cannot change to a different panel address.

 

Solution: Cancel the login by selecting the X in the corner of the error window. Click

 

Connect To Panels and login to one of the existing panels.

 

Graphics Files do not Save Properly

 

Issue: When using some special characters in graphics file names, the files do not

 

save to the panel properly.

 

Solution: You cannot create files which will be saved to the A:\ or B:\ drives that contain

 

any of the following:

 

The following special characters:

 

. \ / : * ? “ < > (includes period)

 

Characters with accent marks (such as é or ô)

 