Chapter 2 - Field Panel Web Server System Administration
Enabling or Disabling Web Server
15
Siemens Industry, Inc. 125-3584T
Be sure that the FPWeb license is installed on the field panel.
HMI S, H, E, W, M (System, Hardware, Ethernet, Webserver, Modify
Example
10:13:04 07/30/2010 FRI Logged on successfully Field panel
<40091>
User: <high> <High default user account>
>Point, Application, Time, Message, Cancel, System, passWord,
Bye? s
>Diagnostics, Users, dSt, Bacnet, Error_msgs, Hardware, Text,
Quit? h
>Fieldpanels, Ethernet, nodeNametable, Disks, Reportprinter,
Licensemanager, Quit? e
>ipSettings, Bbmd, Telnet, Webserver, Quit? w
>Display, Modify, Uiupgrade, Graphicsbackup, Quit? m
>Webserver Enabled (Y/N) : y
>Ok to coldstart (Y/N) : y
Use these procedures to check the enabled/disabled status of Web Server.
HMI S, H, E, W, D (System, Hardware, Ethernet, Webserver, Display
Example
10:13:04 07/30/2010 FRI Logged on successfully Field panel
<40091>
User: <high> <High default user account>
>Point, Application, Time, Message, Cancel, System, passWord,
Bye? s
>Diagnostics, Users, dSt, Bacnet, Error_msgs, Hardware, Text,
Quit? h
>Fieldpanels, Ethernet, nodeNametable, Disks, Reportprinter,
Licensemanager, Quit? e
>ipSettings, Bbmd, Telnet, Webserver, Quit? w
>Display, Modify, Uiupgrade, Graphicsbackup, Quit? d
Webserver Enabled : Enabled