Chapter 5 - Point Commander

 

 

 

 

 

Using the Point Commander Application

 

 

 

 

 

 

 

 

 

 

 

Error Code

 

Situation

 

 

 

 

 

 

 

INVALID_DATATYPE

 

The data type of the value provided is incorrect

 

 

 

for the specified property.

 

 

 

The value provided is outside the range of values

 

VALUE_OUT_OF_RANGE

 

 

 

 

that the property can take on.

 

 

 

There is not enough space to store the new

 

NO_SPACE_TO_WRITE_PROPERTY

 

 

 

 

value.

 

 

 

The data being written has a data type not

 

DATATYPE_NOT_SUPPORTED

 

 

 

 

supported by the property.

 

 

 

 

 

 

Tips for Using the Point Commander Application

Points can be commanded from the Navigation pane or from an animated graphic. See the FINlite Graphics Tool section for information on commanding a point from a graphic.

You can only command points if you have been given Command or higher access level to the point.

Both analog and digital points can be commanded.

Generally, only output points (AO, BO, and MSO) or virtual points (AV, BV, MSV) can be commanded; however, AI and BI input points can be commanded if taken out of service first.

If the same point is commanded from two different sessions, the command with the higher priority will override. If the commands are made with the same priority, the last command will override the earlier command.

Multi State Input Object (MSI) points are not supported on the FLN.

Use caution when moving the Commander window around the screen. If you move it too far up the screen, you may not be able to access the title bar and move the screen back down into view.

Using the Point Commander Application

Commanding Point Values

Commanding a point means using the Point Commander Application to manually override the system program instructions for either an output point or a virtual input point. Point commanding changes the command priority from NONE.

This procedure is only available to users with Command or higher access to points.

 

39

Siemens Industry, Inc.

125-3584T

Page 39
Image 39
Siemens 125-3584T manual Tips for Using the Point Commander Application, Commanding Point Values