Setting the DIP Switches

Set the DIP switches on each 5700 series transmitter to the appropriate

on 5700 Series

zone/ID number and House ID.

Refer to the Compatible 5700 Series

Transmitters

Transmitters table on a following page in this section for zone numbers and

 

 

programming information for each particular transmitter. Refer also to DIP

 

 

SWITCH TABLES FOR 5700 RF WIRELESS DEVICES later in this section.

 

 

 

 

 

The House ID allows the 5700 RF system to identify 5700 transmitters with a

 

 

matching House ID. If using a 5700 RF wireless system, the DIP switches on

 

 

the transmitters must match the system House ID programmed into the

 

 

control (in data field 24). If using a 5827BD wireless keypad, the House ID

 

 

also applies. Other than the 5827 and 5827BD, 5800 series devices do not

 

 

communicate by House ID, but by transmitting a unique serial number to the

 

 

control. In this case, programming a House ID is not necessary.

Wireless Zone/ID Each wireless zone can be assigned any zone response type, such as

Assignments for 5700

Entry/Exit, Interior Follower, Perimeter, etc. (see the ZONE RESPONSE TYPE

Series Transmitters

DEFINITIONS section in the separate Programming Guide for a detailed

explanations of each zone type). For 5700 series transmitters, each response

 

 

 

 

type uses a certain range of zone numbers. Each range of zone/ID numbers is

 

 

shown below.

 

 

 

Zone Type

Transmitter Zone/ID #

 

 

–––––––––––––––––––––––––––

–––––––––––––––––––––––––––––––––––––––––––––––––––––––––

 

 

Entry/Exit Burg

10 through 47 *

 

 

Perimeter Burg

10 through 47 *

 

 

Interior Burg

10 through 47 *

 

 

 

32 through 47 * (5775)

 

 

Fire

48 through 63 *

 

 

 

48 through 55 ** (5706)

 

 

24 Hour Panic

48 through 63 *

 

 

(silent or audible)

62 or 63 *** (5701)

 

 

Day/Night Burglary

10 through 47 *

 

 

24 Hour Auxiliary

10 through 47 *

* Zone/ID numbers 10–63 can be used, but you should note the following in connection with certain transmitter zone/IDs identified as follows:

** Transmitter IDs 48 through 55 have highest signal priority.

*** Transmitter IDs 62 and 63 are unsupervised to allow removal of the 5701 off premises — signal priority is lower than that of fire, but higher than burglary.

Notes: 1. Transmitters set for zone/IDs 48–55 (FIRE) will transmit once every 12 seconds while the zone is faulted. Transmitters set for zone/IDs 56–63 will transmit once every 3 seconds while faulted. These two ranges of zone/ID numbers have high signal priority and their frequent transmissions while faulted ensure re-triggering of the alarm until the cause is removed. Bear in mind that because of this, transmitter battery life could be shortened.

2.Transmitters set for an zone/IDs of 32 through 47 will have a 3-minute lock-out between transmissions. Use this range of zone/ID numbers for sensors protecting frequently used doors or windows to conserve battery life.

3.Refer also to “Compatible 5700 Series Transmitters”on a following page.

– 25 –

Page 25
Image 25
VistaQuest N7227V5 Setting the DIP Switches, On 5700 Series, Refer to the Compatible 5700 Series, Transmitters