STOP (STP): The "STOP" programming determines when and under what conditions the relay will be de-activated. The following options are available:

A)1. RESTORE ZONE LIST (ZL) . If a "ZONE LIST" is used as the “Stop” event, the relay will de-activate whenall the zones in that list restore from a previous fault, trouble, or alarm condition. This will occur regardless of what is programmed to "START" the relay; therefore, a "RESTORE ZONE LIST" would normally only be used when a "ZONE LIST" is used to start the relay.

B)1. ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a "RESTORE ZONE LIST", a specific zone (response) type or system operation action can be selected to de-activate the relay.

If a specific "ZONE TYPE" is chosen, any zone of that response type that restores from a previous alarm, trouble, or fault condition will cause the relay to de-activate.

If a "SYSTEM OPERATION" is chosen, that operation will cause the relay to de-activate. The different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in “Programming Relays” later in this section, and in the Programming Form.

If relay outputs are used, two keypad entries available to the user are included among the system operation choices (34 and 35) that may be programmed. They can manually activate or de-activate the relay(s) for starting or stopping some action, such as turning lights on or off, etc.

These entries are: Security Code + [#] + [7] and Security Code + [#] + [8]

Note: Whichever entry is used to start/stop the action cannot also be used to stop/start it. The opposite action must either be performed by the other keypad entry or by some other event or operation offered in the programming section.

If a relay is energized before a 4-wire smoke detector is reset, the relay will be stopped by the interruption of Aux. Power that resets the smoke detector. If this is not desired, the power to the relay unit should be supplied from another 12V power source (e.g., the same source that is powering ex- ternal equipment through the relay contacts).

Programming Output Relays

1.With at least one 2-line Alpha keypad (5137AD or 6139) connected to the keypad terminals on the control, power up the system temporarily. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power up the system.

2.Enter the programming mode by keying the following on the Alpha keypad:

INSTALLER code (4 1 1 1) + 8 + 0.

Field 25 OUTPUT MODULE must have been programmed for a 4204 module (enter “3”).

3Press 80. Note that this is an interactive menu programming mode. It is used to program all output relays used in the system (4204 Relay modules). Refer to the Programming Form worksheet in the separate PROGRAMMING GUIDE for 80 Interactive Mode.

– 41 –

Page 41
Image 41
VistaQuest N7227V5 installation instructions Programming Output Relays, Installer code 4 1 1 1 + 8 +