APPENDIX I: Monitor Arming Codes
Monitor Arming Codes identify the alarm display, queuing, and clearance methods for armed monitors, as well as the arm type (an abbreviated code that displays on the monitor when an alarm occurs).
The following arming codes are available.
Single Display, Sequence Queuing
•SSI – Single alarm monitor, all alarms are queued and sequenced. Alarms are cleared when the alarm closures is restored (Instant).
•SSI A – Single alarm monitor, all alarms are queued and sequenced. Alarms are cleared when the alarm closure is restored or when the user clears the alarm (Instant or Manual).
•SSA – Single alarm monitor, all alarms are queued and sequenced. Alarms are cleared 20 seconds after the alarm closure is restored (Automatic).
•SSA A – Single alarm monitor, all alarms are queued and sequenced. Alarms are cleared 20 seconds after the alarm closure is restored or when the user clears the alarm (Automatic or Manual).
•SSM – Single alarm monitor, all alarms are queued and sequenced. Alarms are cleared only when the operator clears the alarm (Manual).
Single Display, Hold Queuing
•SHI – Single alarm monitor, all alarms are queued, and the first alarmed contact is displayed and held until cleared. Alarms are cleared when the alarm closure is restored (Instant).
•SHI A – Single alarm monitor, all alarms are queued, and the first alarmed contact is displayed and held until cleared. Alarms are removed from the queue when the alarm closure is restored or when the user clears the alarm (Instant or Manual).
•SHA – Single alarm monitor, all alarms are queued, and the first alarmed contact is displayed and held until cleared. Alarms are removed from the queue 20 seconds after the alarm closure is restored (Automatic).
•SHA A – Single alarm monitor, all alarms are queued, and the first alarmed contact is displayed and held until cleared. Alarms are removed from the queue 20 seconds after the alarm closure is restored or when the user clears the alarm (Automatic or Manual).
•SHM – Single alarm monitor, all alarms are queued, and the first alarmed contact is displayed and held until cleared. Alarms are removed from the queue only when the operator clears the alarm (Manual).
Block Display, Sequence Queuing
•BSI – Multiple monitor alarm block, all alarms are queued and displayed on monitors with no existing alarms. When all monitors have alarms, alarms sequence evenly on all monitors. Alarms are removed from the queue when the alarm closure is restored (Instant).
•BSI A – Multiple monitor alarm block, all alarms are queued and displayed on monitors with no existing alarms. When all monitors have alarms, alarms sequence evenly on all monitors. Alarms are removed from the queue when the alarm closure is restored or when the user clears the alarm (Instant or Manual).
•BSA – Multiple monitor alarm block, all alarms are queued and displayed on monitors with no existing alarms. When all monitors have alarms, alarms sequence evenly on all monitors. Alarms are removed from the queue 20 seconds after the alarm closure is restored (Automatic).
•BSA A – Multiple monitor alarm block, all alarms are queued and displayed on monitors with no existing alarms. When all monitors have alarms, alarms sequence evenly on all monitors. Alarms are removed from the queue 20 seconds after the alarm closure is restored or when the user clears the alarm (Automatic or Manual).
•BSM – Multiple monitor alarm block, all alarms are queued and displayed on monitors with no existing alarms. When all monitors have alarms, alarms sequence evenly on all monitors. Alarms are removed from the queue only when the operator clears the alarm (Manual).
MEGAPOWER CPU ADMINISTRATOR’S GUIDE