Start-Up Procedure: InfraStruXure System
InfraStruXure System—Installation and Start-Up 53
9. Set the Battery Enclosure DC Disconnect circuit breaker to ON.
10. Set the UPS System Enable switch to ON.
When the System Enable switch is in the ON position, the UPS is running on battery. The Startup
screen appears on the display interface of the Symmetra PX UPS, and then
the top-level status screen appears on the display interface. This may take up to 40 seconds.
PowerView RM
Rev: 000 English
Please wait...
Fuel %
Load %
Runtime:
||||||||||||
|||
1hr 2m
In 208V out000V 60Hz