Fuel %
Load %
In 208V out000V 60Hz Runtime: 1hr 2m
Top-Level Menu
Control Logging
Status Display
Setup Diags
Accessories Help
Control Menu
UPS Into Bypass Do Self Test Simulate Power Fail Graceful Reboot
Graceful Turn Off
Start Runtime Cal Turn Load On
Confirmation Screen
Confirm
Yes, UPS Load ON No, Abort
UPS has been
commanded to turn load power on...
Top-Level Status Screen

Start-Up Procedure: InfraStruXure System

When the System Enable switch is in the ON position, the UPS is running on battery. The Startup screen appears on the display interface of the Symmetra PX UPS, and then

PowerView RM

Rev: 000 English

Please wait...

the top-level status screen appears on the display interface. This may take up to 40 seconds.

Fuel %

Load %

In 208V out000V 60Hz

Runtime: 1hr 2m

3. Read the messages displayed on the Symmetra PX UPS display interface: Note any alarms and verify that they are

appropriate for start-up conditions.

4. Command the UPS to apply power to the load: a. Press the ESC key to open the top-level

menu.

b. Select Control, and press the ENTER key.

c. Select Turn Load On/Off from the Control menu, and press the ENTER key.

d. On the next screen: select Yes, UPS Load ON, and press the ENTER key.

The interface will display the following screen:

58

InfraStruXure System—Installation and Start-Up

Page 68
Image 68
American Power Conversion InfraStruXureTM System manual PowerView RM Rev 000 English Please wait