Start-Up Procedure: InfraStruXure System

Verify UPS battery operation

1. Read the messages displayed on the Symmetra PX UPS display interface: Note any alarms and verify that they are

appropriate for start-up conditions.

2. Command the UPS to apply power to the load: a. Press the ESC key to open the top-level

menu.

b. Select Control, and press the ENTER key.

c. Select Turn Load On/Off from the Control menu, and press the ENTER key.

d. On the next screen: select Yes, UPS Load ON, and press the ENTER key.

The interface will display the following screen:

The interface will display the following fault message:

e. Select Start up on Batt, and press the

ENTER key.

The interface will display the following screen:

54

InfraStruXure System—Installation and Start-Up

Page 64
Image 64
American Power Conversion InfraStruXureTM System manual Verify UPS battery operation